Auxiliary Alarm Signaling Equipment - ADEMCO VISTA-50P Installation And Programming Manual

Partitioned security system with scheduling
Hide thumbs Also See for VISTA-50P:
Table of Contents

Advertisement

Auxiliary Alarm Signaling Equipment (Long Range Radio)
– 78 –
The J7 header provides triggers for fire alarm, burglary/audible panic alarm,
silent/duress alarm.. These triggers are programmed as the defaults for Outputs,
2, 3, and 4. These may be used to trip auxiliary alarm signaling equipment such
as Ademco's 7720 and 7920SE Long Range Radios.
The triggers for Fire (Output 2) and Silent Panic/Duress (Output 4) may be used
to operate keyswitch armed and ready LEDs instead when field *15 is enabled.
When used as alarm triggers, these outputs are normally low, and go high when
the corresponding alarm condition occurs. These triggers remain high until the
security code + OFF is entered at the keypad, with the exception of the Silent
Panic/Duress trigger, which is a 2-second pulse. The diagrams that follow show
how to make connections to the 7720 and 7920SE radios. Refer to the UL
Installation
Requirements
REQUIREMENTS section for a description of the specific connections and
programming options required for each of the various UL Listings.
When a Long Range Radio is installed, configure the sense select for zones 1
and 2 in the Long Range Radio to activate on +5V (positive trigger). This is
necessary to prevent false alarms from occurring. Refer to the installation
instructions provided with your radio for instructions on setting the zone 1 and 2
levels.
VISTA-50P OR VISTA-50PUL
7720 WIRING
(USE VISTA-50PUL FOR UL LISTED
COMMERCIAL BURGLARY INSTALLATIONS)
NOTES:
FOR UL LISTED COMMERCIAL BURGLARY
INSTALLATIONS:
1. MOUNT THE 7720 WITHIN 3 FEET OF THE
C-COM. RUN WIRING FROM C-COM TO 7720
IN CONDUIT.
2. CONNECT RADIO FAULT OUTPUT TO C-COM
EOLR SUPERVISED ZONE (ZONE 2-8 ONLY).
USE 2K EOLR.
3. SEE UL INSTALLATION REQUIREMENTS ON A
LATER PAGE TO DETERMINE WHEN 659EN
USAGE IS REQUIRED.
4. CONNECT TO C-COM EOLR SUPERVISED
ZONE (ZONE 2-8 ONLY) WHEN DESIRED TO
HAVE PANEL LOCALLY ANNUNCIATE PHONE
LINE FAULTS.
VISTA-50 OR VISTA-50UL
7920SE WIRING
(USE VISTA-50UL FOR UL LISTED
COMMERCIAL BURGLARY INSTALLATIONS)
J7
NOTES:
FOR UL LISTED COMMERCIAL BURGLARY
INSTALLATIONS:
1. MOUNT THE 7920SE WITHIN 3 FEET OF THE
C-COM. RUN WIRING FROM C-COM TO
7920SE IN CONDUIT.
2. CONNECT RADIO OK OUTPUT TO C-COM
EOLR SUPERVISED ZONE (ZONE 2-7 ONLY).
USE 2K EOLR.
3. SEE UL INSTALLATION REQUIREMENTS ON A
LATER PAGE TO DETERMINE WHEN 659EN
USAGE IS REQUIRED.
4. CONNECT TO C-COM EOLR SUPERVISED
ZONE (ZONE 2-8 ONLY) WHEN DESIRED TO
HAVE PANEL LOCALLY ANNUNCIATE PHONE
LINE FAULTS.
Figure 24: Auxiliary Alarm Signalling Equipment
found
4142TR CABLE
GND
BURG/AUDIBLE PANIC
SILENT PANIC/DURESS
J7
FIRE
28 29 30
TO C-COM
AUX PWR
(35mA DRAW)
}
7 BLACK
659EN LINE FAULT MONITOR
6 RED
+12V GND
ORANGE
YELLOW
1 2 3 4 5 6 7 8
GREEN
PHONE LINE MONITOR
SEE
NOTE 4
(+12V ON FAULT)
OPTIONAL
CONNECT
TO C-COM
EARTH GROUND
SCREW (TB30)
4142TR CABLE
GND (GRAY)
FIRE
SILENT PANIC/DURESS
BURG/AUDIBLE PANIC
28 29 30
TO C-COM
AUX PWR
SEE NOTE 2
(35mA DRAW)
}
7 BLACK
659EN LINE FAULT MONITOR
6 RED
+12V GND
ORANGE
FAULT
YELLOW
GREEN
1 2 3 4 5 6 7 8
SEE
PHONE LINE MONITOR
NOTE 4
(+12V ON FAULT)
OPTIONAL
in
the
REGULATORY
7720 RADIO
SEE 7720 INST. INSTR. FOR
INSTRUCTIONS ON POWERING UNIT
1 2 3 4 5 6 7 8 9 10
(GRAY)
(BROWN) REQUIRED
(BLACK) OPTIONAL
(RED)
OPTIONAL
RADIO FAULT OUTPUT
SEE NOTE 2
(PROGRAM FOR SHORT ON FAULT)
FAULT
PHONE LINE MONITOR
(OPENS ON FAULT)
REQUIRED
INCOMING PHONE LINE
7920SE RADIO
SEE 7920SE INST. INSTR. FOR
INSTRUCTIONS ON POWERING UNIT
EARTH GROUND
CABINET GROUND
TB1
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
TB2
(RED)
OPTIONAL
(BLACK) OPTIONAL
(BROWN) REQUIRED
4.7K (NOT SUPPLIED)
RADIO OK OUTPUT
(LOW ON FAULT)
PHONE LINE MONITOR
(OPENS ON FAULT)
REQUIRED
INCOMING PHONE LINE
AGENCY
FAULT

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vista-50pul

Table of Contents