1 72 EVENT LOG PRINTER ON-LINE MODE
Enter 1 to have the printer print events as they occur.
Enter 0 to enable the printer to print the logs only upon request.
Note: If field 3 19 is not set to 1, the printer will not operate.
1 73 PRINTER BAUD RATE
Enter 0 if printer is set for 1200 baud (preferred).
Enter 1 if printer is set for 300 baud.
Note: Must be 1200 if using the alphanumeric pager interface.
1 74 RELAY TIMEOUT XXX MINUTES
Enter the relay timeout, 000-127 in multiples of 2 minutes, desired for #80 Menu Mode
time-driven event relay command numbers 04/09 and Relay Programming output
command 56 (refer to the Quick Start Guide and Section 24: Scheduling Options in this
manual).
1 75 RELAY TIMEOUT YYY SECONDS
Enter the relay timeout, 000-127 seconds, desired for #80 Menu Mode time-driven event
relay command numbers 05/10 and Relay Programming output command 57 (refer to
the Quick Start Guide and see Section 24: Scheduling Options in this manual).
1 76 ACCESS RELAY # (partition-specific)
The system can be programmed to provide user-activated access control. If enabled, the
assigned relay will pulse for 2 seconds when the user enters his code and presses 0.
Enter the relay number (01-16) for the relay that will be used for access control. Enter
00 if not used in this partition. This function has not been UL Listed for use with the
VISTA-32FB control. Must be 00 for commercial fire and UL.
1 77 LOG FIRST MAINTENANCE SIGNAL
Enter 0 for no logging.
Enter 1 to log first maintenance signal from each smoke detector.
2 00 NUMBER OF PARTITIONS
Enter the number of partitions (1-2) to be used in the system.
2 01 DAYLIGHT SAVINGS TIME START/END MONTH
Enter the months (00-12) in which daylight savings time starts and ends.
Enter 00, 00 if daylight savings time does not apply to the user's region. Standard
setting for U.S. is 04,10.
2 02 DAYLIGHT SAVINGS TIME START/END WEEKEND
Enter the start and end weekends for daylight savings time as follows: 1=first;
2=second; 3=third; 4=fourth; 5=last; 6=next to last; 7=third from last. Standard setting
for U.S. is 1,5.
Section 23 – Data Field Descriptions
[000]
[000]
[04,10]
|
[1,5]
[0]
[0]
|
|
|
|
[00]
|
[0]
[1]
|
23–15