ADEMCO VISTA-32FB Installation And Setup Manual page 137

Fire and burglary partitioned security system with scheduling
Table of Contents

Advertisement

3 20 TRIGGER OUTPUTS FUNCTION SELECTION
Enter 0 for Long Range Radio outputs and Remote Keypad Sounder. Enter 1 for limited
LORRA outputs and Keyswitch LEDs. Enter 2 for LORRA Fire output only and
5140LED connection.
3 21 MAX # OF DIALER ATTEMPTS
Enter the maximum number of attempts to each telephone number, 1-8. Must be 3, 4,
or 5 for NFPA72-compliant systems if a secondary number is programmed.
3 30 DIALER SELECTION
Enter 1 to enable each dialer that exists in the system.
3 31 BACKUP DIALER TOUCHTONE/ROTARY
Enter the dialing method for the system's backup dialer.
Enter 1 for TouchTone, 0 for rotary.
3 50 ZONE TYPE RESTORE ENABLES FOR ZONE TYPES 16-18
Enter 1 for each zone type to send a Restore message to the central station. Default is
[000]. (Must be 1 for commercial fire and UL commercial burglary installations.)
3 55 RESET ON SECOND OFF FOR BELL 1
Enter 0 and the first OFF sequence ([Security Code] + [OFF]) after a fire alarm to de-
activate sounders and/or strobe lights connected to Bell 1 output.
Enter 1 and the second OFF sequence ([Security Code] + [OFF]) after a fire alarm to
de-activate sounders and/or strobe lights connected to Bell 1 output.
3 56 RESET ON SECOND OFF FOR BELL 2
Enter 0 and the first OFF sequence ([Security Code] + [OFF]) after a fire alarm to de-
activate sounders and/or strobe lights connected to Bell 2 output.
Enter 1 and the second OFF sequence ([Security Code] + [OFF]) after a fire alarm to
de-activate sounders and/or strobe lights connected to Bell 2 output.
3 57CONFIRMATION OF ARMING DING BELL 2 and AUX RELAY
Enter 1 to enable 1/2 second external alarm sounding (ding) at the end of exit delay (or
after kissoff from the central station, if sending Closing reports.) Otherwise enter 0.
(Must be 1 for UL installations.)
3 59 ENABLE BELL 2 and AUX RELAY CHIME ANNUNCIATION
Enter 1 to enable the Chime function on Bell Output 2 and the aux. relay. Otherwise
enter 0.
3 60 BELL 2 and AUX RELAY TIMEOUT
Defines the length of time Bell Output 2 and the aux. relay will sound for all audible
alarms (multiply entry 01-15 by 2 minutes for actual duration).
Minimum 16 minutes for UL burglary installations.