Grade A Mercantile Premises Listing; Figure 4.2 Cabinet Attack Resistance Considerations - ADEMCO VISTA-32FB Installation And Setup Manual

Fire and burglary partitioned security system with scheduling
Table of Contents

Advertisement

VISTA-32FB Installation and Set-Up Guide
For UL installations that require certificate burglary service, the optional VISTA-ULKT attack-
U L
resistant enclosure kit and optional 1451 wired-in transformer must be used. Follow the special
installation requirements described in the applicable Grade A Listing sections below.

Grade A Mercantile Premises Listing

The panel door must be supervised. Mount the clip-on tamper switch (supplied with the
VISTA-ULKT enclosure kit) to the cabinet's right-side wall as shown in the diagram
below, and wire it to zone 6.
Use a bell with a tamper-protected housing such as the ADEMCO AB12. The bell
housing's tamper switch and inner tamper linings must also be wired to zone 6.
Assign zone 6 to a burglary partition. Program it for day trouble/night alarm (zone type
5) when only one burglary partition is used. Program it for 24-hr. audible alarm (zone
type 7) when more than one burglary partition is used. Enable the Zone 6 Alternate
Tamper function (program field 3 17).
All wiring between the bell and panel must be run in conduit. Remaining wires do not
need to be run in conduit.
All wiring not run in conduit must exit from the knockout openings on the bottom or back
of the cabinet.
All unused knockouts must be plugged using the disc plugs and carriage bolts (supplied
with the VISTA-ULKT enclosure kit), as indicated in the diagram below.
Fasten the cabinet door to the cabinet backbox using the 18 one-inch-long Phillips-head
screws (supplied with the VISTA-ULKT enclosure kit) after all wiring, programming and
checkout procedures have been completed.
4–2
CABINET ATTACK RESISTANCE CONSIDERATIONS
(Shows typical local Grade A listing installation)
RUN BELL WIRES
PLUG THIS
IN CONDUIT
KNOCK-OUT
C-COM
PCB
PLUG THIS
KNOCK-OUT
1
1
PLUG THIS
RUN ALL REMAINING
KNOCK-OUT
WIRES THRU HERE

Figure 4.2 Cabinet Attack Resistance Considerations

CLIP-ON DOOR
TAMPER SWITCH
CABINET
MOUNTING HOLE
(4 PLACES)
PLUG THIS
KNOCK-OUT
TO PLUG AN UNUSED KNOCKOUT OPENING, REMOVE KNOCKOUT AND
INSTALL A PAIR OF DISC PLUGS AND A CARRIAGE BOLT AS SHOWN:
DISC PLUGS (DIMPLES IN DISC
PLUG SHOULD REGISTER INSIDE
KNOCK-OUT
KNOCK-OUT OPENING
OPENING
CARRIAGE BOLT
HEX NUT AND
CABINET SIDEWALL
LOCK WASHER
(OUTSIDE)