8.3

Handy Functions

This section explains some handy functions of the L series master/local module.
8.3.1
Remote device station initialization procedure registration
function
The initial settings of remote device stations can be performed using GX Works2 for registration to the programmable
controller CPU.
The L series master/local module instructs registration or remote device station initialization procedure (SB000D) and
then stores the number of the currently executing procedure to the buffer memory. For this reason, when processing
has stopped, the relevant information such as the procedure number or target station number can be confirmed. For
details on procedure numbers, refer to
Also, if a running remote device station is replaced due to a failure, initial processing that has been done for all stations
before can be performed for the replaced remote device station by specifying it. Remote device stations other than the
specified station continue to operate.
For example, in an AJ65BT-64AD, settings such as "A/D conversion enable/prohibit specification" and "Averaging
process specification" can be easily configured.
For the availability of this function, refer to the manuals of the remote device stations to be used.
(1) Number of setting items for remote device station initialization procedure
registration
Remote device station initialization procedure registration can be executed up to 16 items per remote device
station.
If setting 17 items or more is necessary, execute initial setting with the program.
The initial processing in the remote device station initialization procedure registration and initial settings with the
program cannot be executed at the same time.
Executing them at the same time may cause remote device station malfunction.
Remote device station initialization procedure registration can be executed up to 16 stations.
When 17 or more remote device stations are connected, execute the initial settings for the 17th and subsequent
stations using the program.
(2) Remote device station initialization procedure setting method
Configure the settings in "Remote Device Station Initial Setting" in the network parameter setting of the master
station, and reflect the initial settings to the remote device station by using the remote device station initialization
procedure registration instruction (SB000D).
For setting examples using GX Works2, refer to
(4), and Page 278, Section 11.3.2 (4).
(1)(b)(9) in Section 8.3.1.
Page 253, Section 11.1.2 (4), Page 265, Section 11.2.2
CHAPTER 8 FUNCTIONS
165
8