(2) Station Information Setting
(a) When the checkbox next to "Set the station information in the CC-Link configuration
window" is checked
There are two ways to set the parameters.
• Set the parameters by automatically detecting the system configuration; and
• Select modules in "Module List" and drag and drop them to "List of stations".
Remark
For how to operate the CC-Link configuration window, refer to the following.
GX Works2 Version 1 Operating Manual (Common)
[Set the parameters by automatically detecting of the system configuration]
The time of setting parameters can be reduced by automatically reading information of device stations
connected to the L series master/local module.
The following lists how to set parameters by automatically detecting the system configuration.
1. Check if the station number of device stations is correctly set.
2. Turn on the device stations first, and turn on a master station.
3. Open the CC-Link configuration window.
Project window
button.
4. [CC-Link Configuration]
Information of the system configuration obtained from the L series master/local module is reflected to the
CC-Link configuration window.
[Parameter]
[Network Parameter]
[Online]
[Detect Now]
CHAPTER 7 PARAMETER SETTINGS
[CC-Link]
[CC-Link Configuration Setting]
7