Mitsubishi Electric L26CPU-BT User Manual page 119

Melsec-l cc-link system master/local module
Hide thumbs Also See for L26CPU-BT:
Table of Contents

Advertisement

[Reading from the remote register (RWr)]
8.
The remote register RWr data of a remote device station is automatically stored in the "remote
register Rwr" buffer memory of the master station.
9.
The remote register RWr data of a remote device station stored in the "remote register RWr" buffer
memory is stored in the CPU device set with the automatic refresh parameters.
Programmable
controller CPU
9)
W
[Remote register RWr when the AJ65BT-64AD is set to station number 1]
Address
RWr0
RWr1
RWr2
RWr3
RWr4
RWr5
RWr6
RWr7
Master station
Remote register RWr
RWr0
RWr1
RWr2
8)
RWr3
RWr4
RWr5
RWr6
RWr7
RWr8
RWr9
RWrA
8)
RWrB
RWrC
RWrD
RWrE
RWrF
RWr10
to
RWrFF
Signal direction: AJ65BT-64AD  Master module
Remote device station
(Station number 1:
occupies 2 stations)
Remote register RWr
Numeric data such as
digital output values,
detected temperature
value, etc.
RWr0
RWr1
RWr2
RWr3
RWr4
RWr5
RWr6
RWr7
Description
CH1 digital output value
CH2 digital output value
CH3 digital output value
CH4 digital output value
Error code
Not used
CHAPTER 8 FUNCTIONS
Remote device station
(Station number 3:
occupies 2 stations)
Remote register RWr
Numeric data such as
digital output values,
detected temperature
value, etc.
RWr0
RWr1
RWr2
RWr3
RWr4
RWr5
RWr6
RWr7
117
8

Advertisement

Table of Contents
loading

This manual is also suitable for:

L26cpu-pbtLj61bt11