(2) Example of check sheet
The following is an example of the check sheet when Microsoft
Confirmation Item
[1]Master Type
1.
Master Station
[2]Master Version
[3]Module Mount Status
[4]Other Network Module
[5]Mode
[6]Parameter
[7]Parameter Setting
[8]Link Start Method
[9]Link Data Access
[10]Transmission Speed
2.
Linked Station
[11]Connected Count
*: The details have been
[12]Station Type*
described to the system
configuration.
[13]Number of Occupied Stations*
[14]CC-Link Version*
[15]Transmission Speed
3.
Transmission Cable
[16]Cable Type
[17]Transmission Distance
[18]Inter-Station Distance
4.
Terminal Resistor
[19]Resistance Value
[20]Connected Terminal
5.
Grounding
[21]FG Terminal
6.
System Configuration
[22]
Station No., Station Type
Number of Occupied Stations
Length of Cable
Contents
Programmable Controller PLC L26CPU-BT
Master Module
L26CPU-BT
Programmable Controller PLC 111110000000000A
Master Module
111110000000000A
I/O Address:
0010H
Other Network Module:
None
Mode Setting:
[*]Remote Net Mode([*]Ver.1/ [ ]Additional /[ ]Ver.2) / [ ]Remote I/O Net Mode
Scan Mode:
[ ]Synchronous/[*]Asynchronous Mode
Module Mode:
[ ]I/O mode / [ ]intelligent mode (SW8:A Series Only)
Checking the parameter matching status between the specification and PLC
Parameter
Number of PLCs
Standby Master Station Setting
PLC Down Drive Specification
Reserved Station
Error Invalid Station
Station Information
[*]GX WORKS2/ [ ]Dedicated Instruction/ [ ]FROM/TO Instruction
[ ]Startup by Buffer Memory:Y6 / [ ]Startup by E2PROM:Y8 (Only QnA, A, FX Series)
[*]Auto Refresh/ [ ]Dedicated Instruction/ [ ]FROM/TO Instruction
[ ]10M/ [ ]5M / [*]2.5M / [ ]625k / [ ]156kbps
Remote I/O Station:0Count, Remote Device Station:0Count, Intelligent Device Station:4Count
[*]Number of occupied stations of each station(Please check it when you confirm it.)
[*]Ver.1 / [ ]Ver2(Expanded Cyclic Setting:[ ]1Times, [ ]2Times, [ ]4Times, [ ]8Times)
[ ]10M/ [ ]5M / [*]2.5M / [ ]625k / [ ]156kbps
Cable Model Name:
Total Extension Distance:
m
Distance between Shortest Station:
m
[*]110ohm / [ ]130ohm / [ ]Not Exist
[ ]Connection between DA-DB of terminal resistor(Please check it when you confirm it.)
[ ]Grounding of FG terminal of each station(Please check it when you confirm it.)
Describe the installation status to "6.System Configuration" when it is not set up in each station.
CHAPTER 15 TROUBLESHOOTING
Excel 2000 or later is installed.
Setting
4Count
None
[*]Stop/[ ]Continue
Station No.3
Station No.4
Written in the system configuration
4Count
15