ST
Constant
(The largest value found in 1) to 3) below. However, 2) is disregarded when B = 0 and 3) is disregarded
when C = 0)
1) 800 + (A  15)
2) 900 + (B  50)
3) For C  26 : 1200 + (C  100), For C > 26 : 3700 + {(C - 26)  25}
EX
Constant (only when remote net ver.2 mode or remote net additional mode is used)
50 + total in the following table
Expanded
cyclic setting
single
double
quadruple
octuple
RT
Retry processing time (only link scans whose device stations became abnormal are added)
 +   (number of stations with communication error detected - 1)
F
Return processing time (only stations with communication errors are added)
BT  {243.1 + 210.8  (number of automatic return modules - 1)} + ST
432
Occupies 1 station
Occupies 2 stations
0
70  Number of stations
80  Number of stations
90  Number of stations 110  Number of stations 130  Number of stations 150  Number of stations
110  Number of stations 160  Number of stations 210  Number of stations 260  Number of stations
Retry processing time on the first station
BY  {(200 + R)  setting value of the number of retries + 178.5}
• When a transient request is made
R: 13.2 + (NI  4.8) + (NW  9.6) + 180
• When no transient request is made
R: 13.2 + (NI  4.8) + (NW  9.6)
Retry processing time on the second and subsequent stations
BT  {(200 + P)  setting value of the number of retries+178.5}
P: 10.8
Number of occupied stations
Occupies 3 stations
0
90  Number of stations 100  Number of stations
Occupies 4 stations
0
0