Item
Select the CC-Link version of the device station.
Select the mode of the L series master/local module if the device station is an
L series master/local module. (Refer to
Version
Select the same CC-Link version as that of the device station actually
connected. If not, data link cannot be performed.
# of STA Occupied
Select the number of occupied stations of the device station.
Select the expanded cyclic setting for the device station. The setting can be
Expanded Cyclic
selected only when "Ver.2 Remote Device Station" or "Ver.2 Intelligent Device
Setting
Station" is set in "Station Type".
The number of points of remote I/O (RX, RY) occupied by the device station is
displayed.
The number of points can be changed for the Ver. 1 remote I/O station when
"Remote Net(Ver.2 Mode)" is set in "Mode Setting". Changing the number of
points can save the areas of a refresh device in a CPU module. (Refer to
When setting eight points to the remote I/O stations, set them to even
numbers of the stations consecutively. When setting eight points to odd
Remote Station Points
numbers of the remote I/O stations, set "8 Points+8 Points (Reserved)" to the
last station of consecutive remote I/O stations.
Master station
Remote output RY
Select whether to set the device station as a reserved station or an error
Reserved/Err Invalid
invalid station. (Refer to
STA
8.3.5, and Page 180, Section 8.3.6.)
Set the size of buffer memory used to perform transient transmission with

dedicated instructions. This setting can be configured only for a local station,
intelligent device station, and standby master station.
Send
Set the size of send buffer to send data using the G(P).RIWT instruction.
Intelligent
Receive
Set the size of receive buffer to receive data using the G(P).RIRD instruction
Buffer Size
(word)
Set the size of automatic update buffer to communicate with an intelligent
Auto
device station using automatic update buffer.
Set the size required for each intelligent device station.
Station-specific mode
Set the station-specific mode for the device station. This setting can be
setting
configured only when the device station supports the station-specific mode.
86
Description
Page 188, Section 8.3.9.)
Remote I/O station
(Station number 1:
Occupies 1 station)
Station
Station
Y07 to Y00
number 2
number 1
Station
reserved
number 3
Station
number 4
8points+8points
(reserved)
to
8-point output module
Page 35, Section 3.4.)
Remote I/O station
Remote I/O station
(Station number 2:
(Station number 3:
Occupies 1 station)
Occupies 1 station)
Y07 to Y00
Y07 to Y00
8-point output module
8-point output module
Page 178, Section 8.3.4, Page 179, Section
Setting range
Varies depending on the module
that was set.
Varies depending on the module
that was set.
Varies depending on the module
that was set.
• 0 Point (Reserved Station)
• 8 Points
• 8 Points+8 Points(Reserved)
• 16 Points
• 32 Points
(Default: Varies depending on
the number of occupied
stations)
Remote I/O station
(Station number 4:
Occupies 1 station)
Y0F to Y00
Y1F to Y10
32-point output module
• No Setting
• Reserved Station
• Error Invalid Station
(Default: No Setting)
0, 64 to 4096
Note that the total buffer size of
"Send" and "Receive" for all
device stations must be 4096 or
less.
(Default: 64)
0, 128 to 4096
Note that the total buffer size of
"Auto" for all device stations
must be 4096 or less.
(Default: 128)
Varies depending on the module
that was set.
