(b) Master station (RWr)  remote device station (RWr)/local station (RWw)
• Master station
• The send data from the remote register (RWr) of the remote device station and the remote register
(RWw) of the local station is stored.
• Four words are used per station.
• Local station
• Data is sent to the master station and other local stations by storing it in the address corresponding to
the host station number.
• Data in the remote register (RWr) of the remote device station can also be received.
• Four words are used per station.
Master station
Address
Remote register (RWr)
2E0
RWr 0
H
2E1
RWr 1
For station
H
number 1
2E2
RWr 2
H
2E3
RWr 3
H
2E4
RWr 4
H
2E5
RWr 5
For station
H
number 2
2E6
RWr 6
H
2E7
RWr 7
H
2E8
RWr 8
H
2E9
RWr 9
For station
H
number 3
2EA
RWr A
H
2EB
RWr B
H
2EC
RWr C
H
2ED
RWr D
For station
H
number 4
2EE
RWr E
H
2EF
RWr F
H
2F0
RWr 10
H
2F1
RWr 11
For station
H
number 5
2F2
RWr 12
H
2F3
RWr 13
H
to
to
3DC
RWr FC
H
3DD
RWr FD
For station
H
number 64
3DE
RWr FE
H
3DF
RWr FF
H
Remote device station
(Station number 1: occupies 1 station)
Remote register (RWr)
RWr 0
RWr 1
RWr 2
RWr 3
Local station
(Station number 2: occupies 4 stations)
Remote register (RWw)
Address
RWw 0
1E0
H
RWw 1
1E1
H
RWw 2
1E2
H
RWw 3
1E3
H
RWw 4
1E4
H
RWw 5
1E5
H
RWw 6
1E6
H
RWw 7
1E7
H
RWw 8
1E8
H
RWw 9
1E9
H
RWw A
1EA
H
RWw B
1EB
H
RWw C
1EC
H
RWw D
1ED
H
RWw E
1EE
H
RWw F
1EF
H
RWw 10
1F0
H
RWw 11
1F1
H
RWw 12
1F2
H
RWw 13
1F3
H
to
to
RWw FC
2DC
H
RWw FD
2DD
H
RWw FE
2DE
H
RWw FF
2DF
H
APPENDICES
A
For station
number 1
For station
number 2
For station
number 3
For station
number 4
For station
number 5
For station
number 64