(2) Remote input (RX) and remote output (RY)
Used when the remote net ver.1 mode, remote net additional mode or remote I/O network mode is selected.
(a) Master station remote I/O station/remote device station/local station
• Master station
• The input data from the remote I/O station, remote device station (RX) and local station (RY) is stored.
• Two words are used per station.
• Local station
• Data to be sent to the master station is stored in the remote output (RY) of the address corresponding
to the host station number.
• The input data from the remote I/O station, remote device station (RX) and other local station is stored.
• Two words are used per station.
Master station
Remote input (RX)
Address
E0
For station
H
number 1
E1
RX 1F to RX 10
H
E2
RX 2F to RX 20
For station
H
number 2
E3
RX 3F to RX 30
H
E4
RX 4F to RX 40
For station
H
number 3
E5
RX 5F to RX 50
H
RX 6F to RX 60
E6
For station
H
number 4
E7
RX 7F to RX 70
H
E8
RX 8F to RX 80
For station
H
number 5
E9
RX 9D to RX 90
H
to
15C
RX7CF to RX7C0
For station
H
number 63
15D
RX7DF to RX7D0
H
15E
RX7EF to RX7E0
For station
H
number 64
15F
RX7FF to RX7F0
H
392
... The last two bits cannot be used for communication between the master
station and the local station.
(In the example below, RY9E and RY9F cannot be used.)
(Station number 1: occupies 1 station)
RX F to RX 0
to
Remote I/O station
X0F
to
X00
X1F
to
X10
Local station
(Station number 2: occupies 4 stations)
Remote output (RY)
Address
RY F to RY 0
160
H
RY 1F to RY 10
161
H
RY 2F to RY 20
162
H
RY 3F to RY 30
163
H
RY 4F to RY 40
164
H
RY 5F to RY 50
165
H
RY 6F to RY 60
166
H
RY 7F to RY 70
167
H
RY 8F to RY 80
168
H
RY 9D to RY 90
169
H
to
to
RY7CF to RY7C0
1DC
H
RY7DF to RY7D0
1DD
H
RY7EF to RY7E0
1DE
H
RY7FF to RY7F0
1DF
H
For station
number 1
For station
number 2
For station
number 3
For station
number 4
For station
number 5
For station
number 63
For station
number 64