Mitsubishi Electric L26CPU-BT User Manual page 369

Melsec-l cc-link system master/local module
Hide thumbs Also See for L26CPU-BT:
Table of Contents

Advertisement

Error code
Error details
(hexadecimal)
Mode invalid (between
B3A0
master and local/standby
master stations)
Standby master setting
B3A1
invalid
Remote I/O net mode
B3A2
station type invalid
B3A3
Assignment error
B3A4
Parameter mismatch
B3A5
Mode invalid (parameter)
B3F1 to B3F3
System error
B401
Parameter change error
B404
Response error
B405
Transient request error
B407
System error
B409
B410
Receive buffer size error
B411
Data length outside of range
Station number outside of
B412
range
B413
Request error
Cause of error occurrence (details)
Model invalid has occurred between the
master and local/standby master stations.
• The mode differs between the master and
standby master stations.
• The local station is set to the remote net
additional mode, and the master station is
set to other than the remote net additional
mode.
• The local station is in the remote net ver.2
mode or remote net additional mode, and
the master station is in the remote net
ver.1 mode.
At the time of parameter setting with
dedicated instruction, an invalid value has
been set to switch 5 of the intelligent function
module switch setting.
At the time of parameter setting with
dedicated instruction, the station type of
other than the remote I/O station has been
set in the remote I/O net mode.
In the remote net Ver.2 mode or remote net
additional mode, total points for remote
stations set in the station information have
exceeded the maximum of 8192.
When the standby master station was
operating as the master station with the
master station duplex function, the network
parameter setting of the faulty master station
was changed.
The mode set in the control data of the
G(P).RLPASET instruction differs from the
mode set with the switch 3 of the intelligent
function module switch setting.
Parameter change was executed during
transient request.
A response from the requested station was
not returned within the watchdog time period.
A transient request was made to a remote
I/O station or a remote device station.
Or, too many transient requests were sent to
the corresponding station.
The receive buffer size of the dedicated
instruction is less than the response data
size.
The number of read/write points in the
control data of the dedicated instruction is
outside the setting range.
The station number in the control data of the
dedicated instruction is outside the setting
range.
Multiple dedicated instructions were
executed for the same station.
CHAPTER 15 TROUBLESHOOTING
Corrective action
After correcting the mismatch of
modes between the master and
local/standby master stations, reset
the CPU module.
Set a correct value to switch 5 of the
intelligent function module switch
setting.
Set all station types to the remote I/O
station.
Check the points for remote stations
in the station information setting.
Return the network parameter
setting of the master station to the
original value.
Check the control data of the
G(P).RLPASET instruction and the
switch 3 setting of the intelligent
function module switch setting.
Please consult your local Mitsubishi
representative.
Change the parameter after all
transient requests are completed or
before any are requested.
Set a longer watchdog time.
If an error persists, check the
requested module and cables.
Set the corresponding station to a
local station or an intelligent device
station.
Or, wait for a while and send the
request again (overload due to many
transient requests).
Please consult your local Mitsubishi
representative.
Check the receive buffer size.
Change the number of read/write
points to within the setting range.
Change the station number to within
the setting range.
Check the program.
Detectability
Master
Local
station
station
15
367