Mitsubishi Electric L26CPU-BT User Manual page 422

Melsec-l cc-link system master/local module
Hide thumbs Also See for L26CPU-BT:
Table of Contents

Advertisement

Number
Name
SW0062
Module operating
(662
)
status
H
SW0064
No. of retries
(664
)
information
H
SW0065
No. of automatic
(665
)
return stations
H
SW0066
Delay timer
(666
)
information
H
SW0067
Parameter
(667
)
information
H
SW0068
Host parameter
(668
)
status
H
SW0069
*3
Loading status
(669
)
H
SW006A
Switch setting status
(66A
)
H
SW006D
Max. link scan time
(66D
)
H
SW006E
Current link scan
(66E
)
time
H
SW006F
Min. link scan time
(66F
)
H
420
Stores the operation setting status of the module.
b15
b14b13
b12b11b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
0 0
0
0
Indicates the retry count setting information when there is an error response.
1 to 7 (times)
Indicates the setting information for the number of automatic return stations during
one link scan.
1 to 10 (stations)
Indicates the delay time setting information.
Stores the parameter information area to be used.
0
: CPU built-in parameters
H
3
: Dedicated instruction (parameter setting with the G(P).RLPASET instruction and
H
data link startup.)
D
: Default parameters (automatically starts CC-Link)
H
Stores the parameter setting status.
0: Normal
Other than 0: Stores an error code (refer to
Stores the duplicate station number status and parameter matching of each station.
0: Normal
Other than 0: Stores the error code (refer to
Details are stored in SW0098 to SW009B and SW009C to SW009F.
Stores the switch setting status.
0: Normal
Other than 0: Stores an error code (refer to
Stores the maximum value of the link scan time (in 1 ms units).
Stores the current value of the link scan time (in 1 ms units).
Stores the minimum value of the link scan time (in 1 ms units).
Description
0
Station type
0: Master station/local station
1: Standby master station (Valid only when b1 is 0)
Master station duplex function
0: Master station duplex function disabled
1: Master station duplex function enabled
Status of input data from a data link faulty station
0: Clear
1: Hold
Number of occupied stations
00: Number of occupied stations: 1
10: Number of occupied stations: 2
11: Number of occupied stations: 3
01: Number of occupied stations: 4
Master station/local station start by dedicated instruction
0: Start by CPU parameter
1: Start by dedicated instruction
Device station refresh/compulsory clear setting in
case of programmable controller CPU STOP
0: Refresh
1: Clears compulsorily
Expanded cyclic setting
00: Single
01: Double
10: Quadruple
11: Octuple
Block guarantee of cyclic data per station
0: Not set
1: Set
Connected devices auto-detection setting
0: Not read the model name of the device stations
1: Read the model name of the device stations
Page 358, Section 15.3).
Page 358, Section 15.3).
Page 358, Section 15.3).