Error code
Error details
(hexadecimal)
Target station specification
error
BC73
(Remote device station
access)
Device No. error
BC74
(Remote device station
access)
All-stations data link error
BC75
(Remote device station
access)
Timeout (Remote device
BC76
station access)
BC81
System error
Message transmission
BC90
result read target module
station number error
Message transmission
BC91
response receive timeout
error
BD83 to BD84
System error
BD85
Hardware error detection
BD86 to BD87
BF11 to BF1C
System error
BF20
BF30 to BF37
Execution result read error
BF38
(Remote device station
access)
Request procedure error
BF39
(Remote device station
access)
BF40 to BF42
System error
Message transmission
BF43
target module station type
error
BF44
System error
Invalid number of messages
BFFA
that were simultaneously
transmitted
Transient request overload
BFFB
error
CPU monitoring timer time
BFFE
out
Error detected in an Ethernet interface module
C000 to CFFF
(Refer to the Ethernet Interface Module User's Manual and the MELSEC-L CPU Module User's Manual (Built-In Ethernet Function).)
Cause of error occurrence (details)
The target of the remote device station
access from the peripheral is a remote I/O
station.
Device No. for "RX", "RY", "RWw", or "RWr"
is outside the valid range for the target
station.
An all-stations data link error occurred during
execution of the remote device station
access from the peripheral.
Timeout occurred during the remote device
station access from the peripheral.
The message transmission result read
request was received from the station with an
unacceptable target station number.
Timeout occurred in receiving message
transmission response data.
A hardware error was detected.
An error is detected in the process of reading
the execution result of the remote device
station access from the peripheral.
An error in the request procedure is detected
during the remote device station access from
the peripheral.
The station type of a target station for the
message transmission is not either a remote
device station or intelligent device station.
The message transmission function was
executed simultaneously for five or more
intelligent device stations.
There are too many transient requests from a
programming tool or GOT.
The CPU monitoring timer timed out.
CHAPTER 15 TROUBLESHOOTING
Corrective action
Check the specified target station
No. and station type.
Check the parameters and valid
device No. of the target station.
Issue the request after starting data
link.
Set a longer timeout time in the
application on the request source, or
check the operation of the target
device station.
Please consult your local Mitsubishi
representative.
Correct the station number of the
target station at the request source,
and execute the function again.
Set a longer Monitoring time setting
(SW0009) and execute the function
again. If the same error occurs
again, check the target station and
cables.
Please consult your local Mitsubishi
representative.
Please consult your local Mitsubishi
representative.
Please consult your local Mitsubishi
representative.
• Check the application of the
request source.
• Check for remote device station
access from another peripheral.
• Check the application of the
request source.
• Check for remote device station
accesses from multiple
peripherals.
• Check if any value is written in the
system area.
Please consult your local Mitsubishi
representative.
Correct the station type of a target
station, and execute the function
again.
Please consult your local Mitsubishi
representative.
Execute four requests or less at the
same time.
Wait for a while and send the
request again.
Check the operation of the target
station.
Detectability
Master
Local
station
station
15
373