6.
Executional condition settings "Execute Condition"
Set the conditions under which initial settings are performed.
Setting range: ON
OFF
7.
Details of execution "Write Device"
Set the device to which the contents of the initial setting are written.
Setting range: RY
RWw
8.
Details of execution "Device No."
Set the device number to which the contents of the initial settings are written.
Even if the target station number is different, the same number must be set.
Setting range: When RY is selected: 0 to 37F (H)
When RWw is selected: 0 to 0F (H)
9.
Details of execution "Write Data"
Set the contents of the initial settings.
Setting range: When RY is selected: ON/OFF
When RWw is selected: 0 to 65535 (Decimal), 0 to FFFF (Hexadecimal)
The following shows the procedure registration window appeared after setting of (1) to (9).
For procedure numbers, the first line of the window is regarded as procedure number 1.
Item of procedure
number1
Item of procedure
number2
CHAPTER 8 FUNCTIONS
167