(1) Operation setting
Project window
Item
Set the parameter name. (Even if the parameter name is not set,
Parameter Name
this will not affect the operation of the CC-Link system).
Select whether to clear or hold data input from a data link faulty
Data Link Faulty
station. (Refer to
Station Setting
Section 8.2.6.)
Select whether to refresh or clear compulsorily output (sending)
data to a device station when the switch on a CPU module is set to
Case of CPU STOP
Setting
STOP. (Refer to
Section 8.2.6.)
Connected Devices
The settings are not required when the L series master/local
Auto-detection
module is used as a local station or standby master station.
Setting
Number of
Set the number of occupied local and standby master station.
Occupied Stations
Select the expanded cyclic setting for the L series master/local
module.
Expanded Cyclic
Select the setting only for the following cases.
Setting
• When "Remote Net(Ver.2 Mode)" or "Remote Net(Additional
Mode)" is set in "Mode"
• When "Local Station" or "Standby Master Station" is set in "Type"
Block Data
Select whether to assure the integrity of cyclic data for each device
Assurance per
station. (Refer to
Station
[Parameter]
[Network Parameter]
Description
Page 133, Section 8.2.4 and Page 136,
Page 134, Section 8.2.5 and Page 136,
Page 159, Section 8.2.9.)
CHAPTER 7 PARAMETER SETTINGS
[CC-Link]
[Operation Setting] button
Setting range
8 characters
(Default: Blank)
• Clear input data (not checked)
• Hold input data (checked)
(Default: Clear input data (not checked))
• Refresh (not checked)
• Clear compulsorily (checked)
(Default: Refresh (not checked))

• Occupied Station 1
• Occupied Station 2
• Occupied Station 3
• Occupied Station 4
(Default: Occupied Station 1)
• Single
• Double
• Quadruple
• Octuple
(Default: Single)
• Disable setting (not checked)
• Enable setting (checked)
(Default: Disable setting (not checked))