Data Link Status Setting In Case Of Master Station Programmable Controller Cpu Failure - Mitsubishi Electric L26CPU-BT User Manual

Melsec-l cc-link system master/local module
Hide thumbs Also See for L26CPU-BT:
Table of Contents

Advertisement

8.2.3
Data link status setting in case of master station
programmable controller CPU failure
This function sets the data link status (stop/continue) in case that an "error that stops the operation" occurs in the
master station programmable controller CPU when the system does not have a standby master station.
When it is set to "continue", the data link among local stations can be continued.
For the status of each station at error occurrence, refer to
● The data link continues when the master station programmable controller CPU falls into an "error that stops the
operation".
● With a standby master station setting, the data link will not continue when the master station programmable controller
CPU is down even if the data link status at CPU down is set to "Continue". The standby master function overrides the
setting and the data link control is switched to the standby master station.
[Setting method]
Specify "PLC Down Select" in the network parameter setting of GX Works2. (Refer to
and Page 99, Section 7.4.2.)
132
Page 136, Section 8.2.6.
Page 77, Section 7.3.2