If the interrupt condition is established upon completion of a link scan, the interrupt is issued. If "Scan Completed"
is set in "Device Code", the interrupt is issued without condition upon completion of a link scan.
Device
Device No.
Code
RX
0 to 1FFF(H)
SB
0 to 01FF(H)
RY
0 to 1FFF(H)
RWr
0 to 07FF(H)
SW
0 to 01FF(H)
Scan
Completed
3. When the interrupt settings are completed, open the "Intelligent Function Module Interrupt Pointer Setting"
window of the PLC parameter.
Relate "Interrupt (SI) No." of the L series master/local module set in the "Interrupt Settings" window to the
interrupt pointer of the CPU module.
Project window
button
4. Input settings to the "Intelligent Function Module Interrupt Pointer Setting" window.
5. Click the [End] button and close the setting window.
94
Detection Method
Interrupt Condition
Edge Detect + ON: Interrupt at rise
Edge Detect + OFF: Interrupt at fall
Level Detect + ON: Interrupt at ON
Level Detect + OFF: Interrupt at OFF
Edge Detect + Equal: Interrupt when the value is
matched (first time only)
Edge Detect + Unequal: Interrupt when the value is
not matched (first time only)
Level Detect + Equal: Interrupt when the value is
matched
Level Detect + Unequal: Interrupt when the value is
not matched

[Parameter]
[PLC Parameter]
Channel
Word Device
No./Connection
Setting Value
No.


0 to 65535
(0(H) to
FFFF(H))
"PLC System" tab
[Interrupt Pointer Setting]
Interrupt
(SI) No.
0 to 15