The following items are automatically reflected to the CC-Link Configuration window:
• Station No.
• Station Type
• Version
• # of STA Occupied Stations
• Expanded Cyclic Setting
*1
When device stations are used as local stations, the stations are displayed as intelligent device stations. Change the
station type if necessary.
5. When a standby master station exists in the system configuration, the station number of the standby
master station is set to the last station number. Change the number corresponding to the actual system
configuration.
6. When the setting is completed, close the CC-Link configuration window by clicking [Close with Reflecting
the Setting].
● When the station number is empty, the following items are displayed as:
• Station Type: Remote I/O Station
• Version: Ver.1
• Number of Occupied Stations: Occupied Station 1
• Expanded Cyclic Setting: Single
• Remote Station Points: 32Points
• Reserve/Invalid Station Select: Reserved
● The connected devices auto-detection function cannot be executed on the station that has switched from a standby
master station to a master station.
To execute the connected devices auto-detection function, follow the procedure below:
1. Turn off a master station and standby master station.
2. Turn on the standby master station, then turn on the master station.
3. Execute the connected devices auto-detection function.
● To execute the connected devices auto-detection function after a system has been changed (for example, addition or
modification of stations), turn on the device stations then the master station.