Mitsubishi Electric L26CPU-BT User Manual page 81

Melsec-l cc-link system master/local module
Hide thumbs Also See for L26CPU-BT:
Table of Contents

Advertisement

Item
Set the start device where data in RX, RY, RWr, and
RWw are transferred. By setting these items, data in
RX, RY, RWr, and RWw can be automatically
Remote Input(RX)
transferred to a device in a CPU module without a
program.
(1) Number of refresh points
Remote Output(RY)
Remote Register(RWr)
(2) Buffer memory areas of the refresh sources
• When "Remote Net(Ver.1 Mode)", "Remote
Net(Additional Mode)", or "Remote I/O Net Mode" is
set in "Mode", data in the Ver.1-compatible area are
transferred to a CPU module.
• When "Remote Net(Ver.2 Mode)" is set in "Mode",
data in the Ver.2-compatible area are transferred to
a CPU module.
(3) To set unique devices
Remote Register(RWw)
• Refresh parameters of modules on the network
• I/O numbers used for I/O modules and an intelligent
function module
• Auto refresh settings of an intelligent function
module
(4) To set X or Y as a refresh device
(5) Refresh timing
Description
All points for the station number 1 to the last
station number are automatically assigned.
(Refer to
Page 392, Appendix 2 (2) and
Page 396, Appendix 2 (3).)
To use a different refresh device for each station,
transfer data in the devices individually using a
program (Un\G or FROM/TO instructions). The
points for each station can be checked using
Device station offset, size information (buffer
memory address: 3E0
to 5DF
H
H
Page 399, Appendix 2 (4).)
(Refer to
Page 392, Appendix 2 (2), Page
396, Appendix 2 (3), Page 405, Appendix 2 (10),
and Page 407, Appendix 2 (11).)
Do not set the same device as the following
items:
Set a unique I/O number used for I/O modules
and an intelligent function module.
Data are refreshed in the END process of a CPU
module.
• Device
X, M, L, B, D, W, R, ZR (X and W for a head
module)
• Device number
Within the device range of the CPU module or head
module
(Default: Blank)
• Device
Y, M, L, B, T, C, ST, D, W, R, ZR (Y and W for a
head module)
• Device number
Within the device range of the CPU module or head
module
(Default: Blank)
• Device
). (Refer to
M, L, B, D, W, R, ZR (W for a head module)
• Device number
Within the device range of the CPU module or head
module
(Default: Blank)
• Device
M, L, B, T, C, ST, D, W, R, ZR (W for a head
module)
• Device number
Within the device range of the CPU module or head
module
(Default: Blank)
CHAPTER 7 PARAMETER SETTINGS
Setting range
7
79

Advertisement

Table of Contents
loading

This manual is also suitable for:

L26cpu-pbtLj61bt11

Table of Contents