Mitsubishi Electric L26CPU-BT User Manual page 83

Melsec-l cc-link system master/local module
Hide thumbs Also See for L26CPU-BT:
Table of Contents

Advertisement

Item
Whether to synchronize the link scan with the
sequence scan of a CPU module or not can be
selected. (Refer to
• Asynchronous
A link scan does not synchronize with a sequence
scan. Input transmission delay time is shortened.
Scan Mode Setting
• Synchronous
A link scan synchronizes with a sequence scan.
(The sequence scan and link scan start
simultaneously.)
Output transmission delay time is shortened.
Because of the synchronization, extended
sequence scan time increases link scan time.
Delay Time Setting
Set 0.
Set information about a device station connected to
Station Information
the master station. (Refer to
Setting
7.3.2 (2).)
Set the procedure for the initial settings when
registering the initial settings of a remote device
Remote Device Station
Initial Setting
station using a programming tool. (Refer to
Page 90, Section 7.3.2 (3).)
Set the conditions used to issue a request for the
Interrupt Settings
interrupt to a CPU module. (Refer to
Section 7.3.2 (4).)
Description
Page 182, Section 8.3.7.)
Page 83, Section
Page 93,
CHAPTER 7 PARAMETER SETTINGS
Setting range
• Asynchronous
• Synchronous
(Default: Asynchronous)
0



7
81