Station Status At Error Occurrence - Mitsubishi Electric L26CPU-BT User Manual

Melsec-l cc-link system master/local module
Hide thumbs Also See for L26CPU-BT:
Table of Contents

Advertisement

8.2.6

Station status at error occurrence

This section explains the status of each station that is set in network parameter's "PLC Down Select" and "Operation
Setting" in case of error occurrence. (Refer to
Section 8.2.5.)
(1) Status of the master station, standby master station (acting as a master
station) and remote I/O station at error occurrence
The following shows the operations of the master station, standby master station (acting as a master station) and
remote I/O station upon the occurrence of an error.
Data link status
When data link is stopped due to an error generated
by the master station programmable controller CPU
(data link continue)
When data link is stopped due to an error generated
by the local station programmable controller CPU
(data link continue)
The GX Works2 data
When data link for
link faulty station is
the entire system is
set (master station
stopped
setting)
When a
The GX Works2 data
communication error
link faulty station is
(power off, etc.)
set (master station
occurs in a remote
setting)
I/O station
When a
The GX Works2 data
communication error
link faulty station is
(power off, etc.)
set (master station
occurs in a remote
setting)
device station
136
Page 132, Section 8.2.3, Page 133, Section 8.2.4 and Page 134,
Master station, standby master station (acting as a
master station)
Remote
Remote
output
input (RX)
(RY)
*1
Continue
*2
Continue
Clear
Clear
Undefined
Hold
Hold
Clears the
receive area
from the
remote I/O
Clear
station having
a
communication
error
Continue
Retains the
receive area
from the
Hold
remote I/O
station with a
communication
error
Clears the
receive area
from the
Clear
remote device
station with a
communication
error
Continue
Retains the
receive area
from the
Hold
remote device
station with a
communication
error.
Remote
Remote
register
register
(RWw)
(RWr)
Continue
Hold
Continue
Continue
Undefined
Hold
Continues
Continues
operation of
operation of
areas other
areas other
than the
than the
remote I/O
remote I/O
station
station
Retains the
receive area
from the
Continue
remote device
station with a
communication
error
Remote I/O station
Input
Output
*1
Continue
Continue
Continue
By external
All points OFF
signals
By external
All points OFF
signals
Continue
Continue
(Not affected
(Not affected
by the
by the
communication
communication
status of the
status of the
remote device
remote device
station)
station)