Secured 32-bit data

When the following conditions, 1) and 2) are satisfied in the CC-Link network, 32-bit data in remote registers
(RWr/RWw) between a programmable controller CPU and a master/local station can be secured.
1) Access starts from a remote resister (RWr/RWw) address of an "even number".
Programmable
Master station
controller CPU
CPU device
Remote register
W000
W001
W002
W003
*Because the start address on the remote resister side is an "odd address", new and old data may be mixed in 16-bit
(1-word) units.
2) Access by the program must be made in units of even points.
Programmable
controller CPU
CPU device
W000
W001
W002
W003
*Because the access is made for each single point (1-word), new and old data may be mixed in 16-bit (1-word) units.
164
Local station
Remote register
RWr00
RWw00
RWr01
RWw01
RWr02
RWw02
RWr03
RWw03
Master station
Remote register
DFRO
RWr00
RWr01
RWr02
RWr03
Programmable
Master station
controller CPU
CPU device
Remote register
W000
RWr00
W001
RWr01
W002
RWr02
W003
RWr03
W004
RWr04
Programmable
controller CPU
CPU device
FROM
W000
W001
W002
W003
Local station
Remote register
RWw00
RWw01
RWw02
RWw03
RWw04
Master station
Remote register
RWr00
RWr01
RWr02
RWr03