Mitsubishi Electric L26CPU-BT User Manual page 175

Melsec-l cc-link system master/local module
Hide thumbs Also See for L26CPU-BT:
Table of Contents

Advertisement

5.
Interrupt condition
Set the conditions under which events are issued.
When RX, SB or RY is selected ON/OFF
Setting range:
When RWr or SW is selected Equal/Unequal
6.
Word device setting value
Set the conditions under which events are issued when RWr or SW is selected.
0 to 65535 (Decimal)
Setting range:
0 to FFFF (Hexadecimal)
7.
Interrupt (SI) No.
Set the intelligent function module interrupt pointer number.
(SI is an interrupt pointer for an intelligent function module and not a device used in an actual program.)
Setting range: 0 to 15
Only one event issuance condition can be set for each interrupt program.
(b) Select "PLC Parameter" -- "PLC System" -- "Intelligent Function Module Setting" --
"Interrupt Pointer Setting".
1.
"Interrupt Pointer Start No." on the PLC side.
Set the interrupt pointer start number for the CPU.
Setting range: 50 to 255
2.
"Interrupt Pointer Count" on the PLC side
Set the number of event issuance conditions specified in the "Interrupt Setting" of the network parameter
setting
Setting range: 1 to 16
3.
"Start I/O No." on the intelligent module side
Set the start input/output number for the intelligent function module for which the interrupt setting was
performed.
Setting range: Within the range of I/O points of the CPU module
CHAPTER 8 FUNCTIONS
173
8