(4) Precautions on the mode between the master/local station and the standby
master station
In any of the following cases, an error (error code: B3A0
If an error has occurred, correct the that for the master, local, or standby master station, and reset the CPU
module.
• The mode set for the master station differs from that for the standby master station.
• When the master station is set to the remote net ver.1 mode, the local station is set to the remote net ver.2
mode or remote net additional mode.
• When the master station is set to the remote net ver.2 mode, the local station is set to the remote net
additional mode.
(5) Automatic refresh setting
(a) By specifying refresh devices, automatic refresh is performed in the END process of
the CPU module.
The automatic refresh covers the areas from the station No.1 to the last station No. set in the network
parameter setting (including occupied stations).
(b) When the remote net additional mode is selected, data of the station No.1 to the last
Ver.1-compatible station (including occupied stations) and data of Ver.2-compatible
stations from its first station No. (the last Ver.1-compatible station No. +1) to the last
station No. are automatically refreshed to devices specified in the first and last
halves respectively.
(c) In the Ver.2-compatible remote register, data in the area up to the last remote device
or intelligent device station No. are refreshed.
The remote net additional mode, Ver.1-compatible station: No. 1 to 8, Ver.2-compatible station: No. 9 to
16 (occupying 1 station, quadruple setting), refresh devices (first half): Y1000, and refresh devices (last
half): Y1100 are set
Programmable
controller CPU
Y0000
Y1000
Y10FF
Y1100
Y12FF
CHAPTER 7 PARAMETER SETTINGS
) will occur at a local or standby master station.
H
Master station
remote output
Station No.1
160
H
Station No.8
16F
H
Master station
Ver.2 compatible remote output
4200
H
Station No.9
4210
H
Station No.16
421F