(3) Remote Device Station Initial Setting
Register the initial settings using a programming tool, and reflect them to a remote device station using Remote
device station initialization procedure registration instruction (SB000D).
Project window
In "Target Station No.", set the station number of the remote device station where the initial settings are
1.
configured.
Set the start station number instead if the number of occupied stations is two or more.
2. Click the [Regist Procedure] button.
Register the procedure for the initial settings in the "Remote Device Station Initial Setting Procedure
3.
Registration" window.
4. Click the [End] button and close the setting window.
• "Remote Device Station Initial Setting Target Station Number Setting" window
Item
Target Station No.
No. of Registered
Procedures
[Regist Procedure]
• "Remote Device Station Initial Setting Procedure Registration" window
Item
Input Format
Execute Flag
Operational Condition
90
[Parameter]
[Network Parameter]
Description
Set the station number of the station where the initial settings are
configured.
The number of the procedures registered using the [Regist Procedure]
button is displayed.
"Remote Device Station Initial Setting Procedure Registration" is
displayed by clicking it.
Select the input format of "Write Data".
Select whether to actually execute the registered procedure or not.
Click it to change the setting.
Set "Only Set" to use the setting only as a reference when inputting
similar setting items.
Select whether to newly set the condition for the initial settings or use
the same condition as the above line.
[CC-Link]
Description
[Initial Setting] button
Setting range
1 to 64 (Default: Blank)


Setting range
• DEC
• HEX
(Default: DEC)
• Execute
• Only Set
(Default: Execute)
• Set New
• Same as Prev. Set
(Default: Set New)