7.5

Precautions on the Parameter Setting

(1) Station number setting
The following explains how to set the station numbers for the master station and device stations.
Specify the station numbers according to the following conditions.
• Set the station numbers not used for other stations. If a station number already in use is set, an error occurs.
• Set consecutive station numbers for stations in the same system. To set empty station numbers for future
use, set the stations as reserved stations. Setting the stations as reserved stations prevents the stations
from being detected as a faulty station. Set reserved stations in the master station using the network
parameter of a programming tool. (
• When the number of occupied stations in a module is two or more, set the start station number.
Station number setting in modules when the number of occupied stations is two or more
Master station
Station No.0
Setting the station numbers 1 to 3 (number of occupied stations: 3) as reserved stations
Master station
Station No.0
● If an empty station number is set without setting a reserved station, the station is detected as a faulty station in Other
station data link status (SW0080 to SW0083).
● The station numbers need to be consecutive, but wiring does not need to be performed in the order of station number.
Page 83, Section 7.3.2 (2), Page 178, Section 8.3.4)
Device station
(Number of occupied stations: 3)
Station No.1 Station No.2 Station No.3
: Station numbers set for the modules
<Reserved station>
Device station
(Number of occupied stations: 3)
Station No.1 Station No.2 Station No.3
: Station numbers set for the modules
CHAPTER 7 PARAMETER SETTINGS
Device station
(Number of occupied stations: 2)
Station No.4 Station No.5
Device station
(Number of occupied stations: 2)
Station No.4 Station No.5