Item
Ver.2 Remote Input(RX)
When "Remote Net(Additional Mode)" is set in
"Mode", set the start device where data in RX, RY,
Ver.2 Remote
RWr, and RWw (Ver.2-compatible area) of the L series
Output(RY)
master/local module are transferred.
Ver.2 Remote
(1) Number of refresh points
Register(RWr)
Ver.2 Remote
Register(RWw)
The other contents are same as those for "Remote
Input(RX)" described the above.
Special Relay(SB)
Set the start device where data in SB and SW are
transferred. The data in SB and SW can be
automatically transferred to a device in a CPU module
without a program.
Special Register(SW)
Set the number of retries for when a communication
Retry Count
failure occurs.
Set the number of device stations that return to the
system operation by a single link scan after the
Automatic Reconnection
stations are disconnected due to a communication
Station Count
failure.
Setting a larger number extends link scan time of
when the station returns.
Set the station number for the standby master station.
Set the station number of the station that controls a
Standby Master Station
CC-Link system instead of the master station if a
No.
master station goes down. (Refer to
Section 8.2.7.)
Select whether to stop or continue data link if a stop
PLC Down Select
error occurs in a CPU module. (Refer to
132, Section 8.2.3.)
80
Description
All points for the start station number to the last
station number of a Ver.2-compatible device
station are automatically assigned. (Refer to
Page 405, Appendix 2 (10) and Page
407, Appendix 2 (11).)
To use a different refresh device for each station,
transfer the data in the devices individually using
a program (Un\G or FROM/TO instructions).
The points for each station can be checked using
Device station offset, size information (buffer
memory address: 3E0
to 5DF
H
Page 399, Appendix 2 (4).)
Same as "Remote Input(RX)"
Same as "Remote Output(RY)"
Same as "Remote Register(RWr)"
Same as "Remote Register(RWw)"
). (Refer to
H
• Device
M, L, B, D, W, R, SB, ZR (W and SB for a head
module)
• Device number
Within the device range of the CPU module or head
module
(Default: Blank)
• Device
M, L, B, D, W, R, SW, ZR (W and SW for a head
module)
• Device number
Within the device range of the CPU module or head
module
(Default: Blank)
1 to 7 (Default: 3)
1 to 10 (Default: 1)
• Blank
• 1 to 64
(Default: 64)
Page 140,
• Stop
• Continue
Page
(Default: Stop)
Setting range

Advertisement