Advertisement

5. When the initial settings are completed, write the settings to the CPU module using a programming tool.
[Online]
6. The settings are reflected by resetting the CPU module or powering off and on the system.
7. Turn on Remote device station initialization procedure registration instruction (SB000D) and start the initial
settings.
While the initial settings are being executed, Execution status of remote device station initialization
procedure (SB005E) is on.
Also, the execution procedure number and the target station number for the procedure registration are
stored in Remote device station initialization procedure registration execution individual information
(SW0110 to SW011F).
8. When the initial settings are completed for all the set stations, Completion status of remote device station
initialization procedure (SB005F) is turned on.
Also, the execution results are stored in Remote device station initialization procedure registration
instruction result (SW005F).
The data stored in Remote device station initialization procedure registration execution individual
information (SW0110 to SW011F) become FF**
settings.)
9. Turn off Remote device station initialization procedure registration instruction (SB000D).
Remote device station initialization procedure registration instruction results (SW005F) and Remote
device station initialization procedure registration execution individual information (SW0110 to SW011F)
are cleared.
The following figure shows the operations of a link special relay (SB) and link special register (SW) when the
remote device station initialization procedure registration is performed.
Specification of remote device
station to be initialized
Remote device station
initialization procedure
registration instruction
Remote device station
initialization procedure
registration execution status
Remote device station initialization
procedure registration completion
status
Remote device station
initialization procedure registration
execution individual information
92
[Write to PLC]
SW0014
to
SW0017
ON
SB000D
OFF
ON
SB005E
OFF
ON
SB005F
OFF
SW00110
to
SW0011F
. (** represents the target station number for the initial
H
Performed by the L series Master/local module
Performed by program