CHAPTER 11 EXAMPLE OF COMMUNICATION BETWEEN THE MASTER STATION AND REMOTE DEVICE STATIONS
(4) Initial setting of the remote device station
(a) Setting the target station number
Set the target station for which the initial setting is performed.
1.
Setting the target station number
Set the target station numbers to "1" and "4".
2.
Selecting the Regist Procedure
Click the "Regist Procedure" of the target station number "1".
(b) Setting the regist procedure registration
Set the conditions and details of the remote device station settings.
For more detailed information about the settings, refer to the User's Manual for the remote device station.
In this section, AJ65VBTCU-68ADVN and AJ65VBTCU-68DAVN are used as examples for the procedure
registration.
1.
Procedure registration of AJ65VBTCU-68ADVN
The details to be set are as follows:
• Set channels 1, 2 to A-D conversion enable (the first condition).
• Set the Input range of channel 1 to 0 - 5V, and channel 2 to User range setting 1 (the second condition).
• Set channel 1 to Sampling processing, and specify channel 2 as Average processing and set it to Number
of times (the third condition).
• Set channel 2 Average number of times to 16 times (the forth condition).
• Turn the Initial data processing completed flag to ON (the fifth condition).
• Turn the Initial data setting request flag to ON (the sixth condition).
• Turn the Initial data processing completed flag to OFF (the seventh condition).
• Turn the Initial data setting request flag to OFF (the eighth condition).
11
265