Item
The number of points of remote I/O (RX, RY) occupied by the device station is
displayed.
The number of points can be changed for the Ver. 1 remote I/O station when
"Remote Net(Ver.2 Mode)" is set in "Mode Setting". Changing the number of
points can save the areas of a refresh device in a CPU module. (Refer to
When setting eight points to the remote I/O stations, set them to even
numbers of the stations consecutively. When setting eight points to odd
Remote Station Points
numbers of the remote I/O stations, set "8 Points+8 Points(Reserved) to the
last station of consecutive remote I/O stations.
Master station
Remote output RY
Station
number 2
reserved
Station
number 4
8points+8points
(reserved)
Select whether to set the device station as a reserved station or an error
Reserve/Invalid Station
invalid station. (Refer to
8.3.5, and Page 180, Section 8.3.6.)
Set the size of buffer memory used to perform transient transmission with

dedicated instructions. This setting can be configured only for an intelligent
device station.
Send
Set the size of send buffer to send data using the G(P).RIWT instruction.
Intelligent
Receive
Set the size of receive buffer to receive data using the G(P).RIRD instruction.
Buffer Select
(Word)
Set the size of automatic update buffer to communicate with an intelligent
Auto
device station using automatic update buffer.
Set the size required for each intelligent device station.
Description
Page 188, Section 8.3.9.)
Remote I/O station
Remote I/O station
(Station number 1:
(Station number 2:
Occupies 1 station)
Occupies 1 station)
Station
Y07 to Y00
number 1
Station
number 3
to
8-point output module
8-point output module
Page 178, Section 8.3.4, Page 179, Section
Remote I/O station
Remote I/O station
(Station number 3:
(Station number 4:
Occupies 1 station)
Occupies 1 station)
Y07 to Y00
Y07 to Y00
Y0F to Y00
Y1F to Y10
8-point output module
32-point output module
CHAPTER 7 PARAMETER SETTINGS
Setting range
• 0 Points(Reserved Station)
• 8 Points
• 8 Points+8 Points(Reserved)
• 16 Points
• 32 Points
(Default: Varies depending on
the "Number of Occupied
Stations".)
• No Setting
• Reserved Station
• Invalid Station
(Default: No Setting))

0, 64 to 4096
Note that the total buffer size of
"Send" and "Receive" for all
device stations must be 4096 or
less.
(Default: 64)
0, 128 to 4096
Note that the total buffer size of
"Auto" for all device stations
must be 4096 or less.
(Default: 128)