(1) Functions
(a) Operation chart for the G(P).RITO instruction
Master station
Programmable controller CPU
Command
G(P).RITO
1)
Device memory
2)
1) Accesses the device after the device specified by (D) of the master module specified by Un.
2) Writes to the automatic update buffer specified by n1 and n2.
(b) The G(P).RITO instruction writes data when it is executed.
However, this instruction cannot be executed simultaneously at more than one location for the same intelligent
device station.
(c) The maximum points that can be read by the G(P).RITO instruction are 4096.
(d) The basic number of steps of the G(P).RITO instruction is 9 steps.
(e) Use GX Works2 to assign automatic update buffer in "Station Information Setting" in
the "Network Parameter" window.
For more details on the setting, refer to
Specified station
Master module
Communication
commences
when
conditions
are met
Automatic
update buffer
Page 83, Section 7.3.2 (2).
CHAPTER 9 DEDICATED INSTRUCTIONS AND PROGRAMMING
Buffer memory
Automatic update
buffer memory
Intelligent device station
219