Mitsubishi Electric L26CPU-BT User Manual page 235

Melsec-l cc-link system master/local module
Hide thumbs Also See for L26CPU-BT:
Table of Contents

Advertisement

Parameter registration (data link startup)
Processing at completion of the G(P).RLPASET instruction
Start of the control program
Refresh of RX
Refresh of RWr
Station number 1 control program
Station number 2 control program
Station number 3 control program
Refresh of RWw
Refresh of RY
*2 D150 and D160 are dummy devices.
CHAPTER 9 DEDICATED INSTRUCTIONS AND PROGRAMMING
Performs abnormal completion processing
Station number 1 control program
Station number 2 control program
Station number 3 control program
Dedicated instruction (G(P).RLPASET)
Turn the parameter setting instruction off.
Instruct to refresh at normal completion
of the G(P).RLPASET instruction.
Instruct to start the control program at
normal completion of the G(P).RLPASET
instruction.
RX00 to RX5F are read to X1000 to
X105F.
RXr0 to RWr3 are read to D1000 to
D1003.
D2000 to D2003 are written into RWw0
to RWw3
Y1000 to Y105F are written into RY00 to
RY5F
233
9
*2