Mitsubishi Electric L26CPU-BT User Manual page 458

Melsec-l cc-link system master/local module
Hide thumbs Also See for L26CPU-BT:
Table of Contents

Advertisement

(2) Remote net additional mode
[Expression]
KM1+KM2
+(Number of CC-Link modules-1) KM4 [ms]
E=KM3
RX:
Points of the remote input (RX) refreshed by the master/local station
RX2:
Points of the ver.2 remote input (RX) refreshed by the master/local station
RY:
Points of the remote output (RY) refreshed by the master/local station
RY2:
Points of the ver.2 remote output (RY) refreshed by the master/local station
RWw:
Points of the remote register (RWw) refreshed by the master/local station
RWw2:
Points of the ver.2 remote register (RWw) refreshed by the master/local station
RWr:
Points of the remote register (RWr) refreshed by the master/local station
RWr2:
Points of the ver.2 remote register (RWr) refreshed by the master/local station
SB:
Points of the link special relay (SB) refreshed by the master/local station
SW:
Points of the link special register (SW) refreshed by the master/local station
E:
Transfer time of the file register (R, ZR), extended data register (D), and extended link register (W) on
the standard RAM (only when the registers are used)
KM1, KM2, KM3, KM4: Constant
CPU type
L02SCPU, L02SCPU-P
L02CPU, L02CPU-P
L06CPU, L06CPU-P,
L26CPU, L26CPU-P,
L26CPU-BT, L26CPU-PBT
Head module
CPU type
L02SCPU, L02SCPU-P
L02CPU, L02CPU-P
L06CPU, L06CPU-P,
L26CPU, L26CPU-P,
L26CPU-BT, L26CPU-PBT
Head module
456
RX+RX2+RY+RY2+SB
16
RX+RX2+RY+RY2+SB
16
Master
station/Local
With block guarantee of cyclic
station
data per station function set
Master station
Local station
Master station
Local station
Master station
Local station
Master station
Local station
-3
KM2 ( 10
When
connected to
connected to
an extension
a main block
0.33
0.36
0.36
0.35
+RWw+RWw2+RWr+RWr2+SW
+RWw+RWw2+RWr+RWr2+SW
0.88
0.91
0.20
0.21
0.18
0.19
0.45
0.71
)
KM3 ( 10
When
When
connected to
a main block
block
0.95
0.03
0.85
0.03
0.85
0.03
0.05
+ E
KM1
Without block guarantee of
cyclic data per station
function set
0.85
0.85
0.18
0.19
0.16
0.17
0.26
0.53
-3
)
When
connected to
an extension
block
0.03
0.03
0.03
KM4
0.2
0.14
0.14
0.2