Siemens CU240B-2 Parameter Manual page 320

Table of Contents

Advertisement

Parameters
List of Parameters
p3322[0...n]
Fluid flow machine P = f(n), Y coordinate: P flow2 %, point 2 / Fluid flow mach Y2
Access level: 2
Can be changed: U, T
Units group: -
Min
0.00
Description:
The power (P) for point 2 on the Y coordinate of the flow characteristic is saved in p3322. Unit: %
Dependency:
Refer to: p3323
Note:
The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
p3323[0...n]
Fluid flow machine P = f(n), X coordinate: n flow2 %, point 2 / Fluid flow mach X2
Access level: 2
Can be changed: U, T
Units group: -
Min
0.00
Description:
The speed (n) for point 2 on the X coordinate of the flow characteristic is saved in p3323. Unit: %
Dependency:
Refer to: p3322
Note:
The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
p3324[0...n]
Fluid flow machine P = f(n), Y coordinate: P flow3 %, point 3 / Fluid flow mach Y3
Access level: 2
Can be changed: U, T
Units group: -
Min
0.00
Description:
The power (P) for point 3 on the Y coordinate of the flow characteristic is saved in p3324. Unit: %
Dependency:
Refer to: p3325
Note:
The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
p3325[0...n]
Fluid flow machine P = f(n), X coordinate: n flow3 %, point 3 / Fluid flow mach X3
Access level: 2
Can be changed: U, T
Units group: -
Min
0.00
Description:
The speed (n) for point 3 on the X coordinate of the flow characteristic is saved in p3325. Unit: %
Dependency:
Refer to: p3324
Note:
The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
1-320
Calculated: -
Scaling: -
Unit selection: -
Max
100.00
Calculated: -
Scaling: -
Unit selection: -
Max
100.00
Calculated: -
Scaling: -
Unit selection: -
Max
100.00
Calculated: -
Scaling: -
Unit selection: -
Max
100.00
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
50.00
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
25.00
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
77.00
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
50.00