Siemens CU240B-2 Parameter Manual page 230

Table of Contents

Advertisement

Parameters
List of Parameters
p1764[0...n]
Motor model without encoder speed adaptation Kp / MotMod woE n_adaKp
Access level: 4
Can be changed: U, T
Units group: -
Min
0.000
Description:
Sets the proportional gain of the controller for speed adaptation without encoder.
r1765
Motor model, speed adaptation Kp effective / MotM n_ada Kp act
Access level: 4
Can be changed: -
Units group: -
Min
-
Description:
Displays the effective proportional gain of the controller for the speed adaptation.
p1767[0...n]
Motor model without encoder speed adaptation Tn / MotMod woE n_adaTn
Access level: 4
Can be changed: U, T
Units group: -
Min
1 [ms]
Description:
Sets the integral time of the controller for speed adaptation without encoder
r1768
Motor model, speed adaptation Vi effective / MotM n_ada Vi act
Access level: 4
Can be changed: -
Units group: -
Min
-
Description:
Displays the effective gain of the integral component of the controller for speed adaptation.
r1770
CO: Motor model speed adaptation proportional component / MotMod n_adapt Kp
Access level: 4
Can be changed: -
Units group: 3_1
Min
- [rpm]
Description:
Displays the P component of the controller for speed adaptation.
r1771
CO: Motor model speed adaptation I comp. / MotMod n_adapt Tn
Access level: 4
Can be changed: -
Units group: 3_1
Min
- [rpm]
Description:
Displays the I component of the controller for speed adaptation.
1-230
Calculated: p0340 = 1,3,4
Scaling: -
Unit selection: -
Max
100000.000
Calculated: -
Scaling: p2001
Unit selection: -
Max
-
Calculated: p0340 = 1,3,4
Scaling: -
Unit selection: -
Max
200 [ms]
Calculated: -
Scaling: p2001
Unit selection: -
Max
-
Calculated: -
Scaling: p2000
Unit selection: p0505
Max
- [rpm]
Calculated: -
Scaling: p2000
Unit selection: p0505
Max
- [rpm]
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
1000.000
Data type: FloatingPoint32
Data set: -
Factory setting
-
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
4 [ms]
Data type: FloatingPoint32
Data set: -
Factory setting
-
Data type: FloatingPoint32
Data set: -
Factory setting
- [rpm]
Data type: FloatingPoint32
Data set: -
Factory setting
- [rpm]
© Siemens AG 2011 All Rights Reserved

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120Cu240e-2Cu240b-2 dpCu240e-2 dpCu240e-2 fCu240e-2 dp f

Table of Contents