p9348
SI Motion SAM actual velocity tolerance (Motor Module) / SI Mtn SAM tol MM
Access level: 3
CU240E-2 DP F
Can be changed: C(95)
CU240E-2 F
Units group: -
Min
0.00 [rpm]
Description:
Sets the velocity tolerance for the "SAM" function.
Dependency:
Refer to: p9548
Refer to: C01706
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
SAM: Safe Acceleration Monitor (safe acceleration monitoring)
p9351
SI Motion SLS changeover delay time (processor 2) / SI Mtn SLS t P2
CU240E-2 DP F
Access level: 3
CU240E-2 F
Can be changed: C(95)
Units group: -
Min
0.00 [µs]
Description:
Sets the delay time for the SLS changeover for the function "safely limited speed" (SLS).
When transitioning from a higher to a lower safely-limited velocity/speed stage, within this delay time, the "old"
velocity stage remains active.
Even if SLS is activated from non safety-related operation, then this delay is still applied.
Dependency:
Refer to: p9551
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
SLS: Safely-Limited Speed
p9356
SI Motion pulse suppression delay time (processor 2) / SI Mtn IL t_del P2
CU240E-2 DP F
Access level: 3
CU240E-2 F
Can be changed: C(95)
Units group: -
Min
0.00 [µs]
Description:
Sets the delay time for the safe pulse suppression after STOP B / SS1.
In the case of encoderless motion monitoring functions with brake ramp monitoring (p9306 = 1), the parameter has
no effect.
Dependency:
Refer to: p9360, p9556
Refer to: C01701
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
SS1: Safe Stop 1
p9358
SI Motion acceptance test mode time limit (processor 2) / SI Mtn acc t P2
CU240E-2 DP F
Access level: 3
CU240E-2 F
Can be changed: C(95)
Units group: -
Min
5000000.00 [µs]
Description:
Sets the maximum time for the acceptance test mode.
If the acceptance test mode takes longer than the selected time limit, then the mode is automatically terminated.
Dependency:
Refer to: p9558
Refer to: C01799
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
1-338
Calculated: -
Scaling: -
Unit selection: -
Max
120000.00 [rpm]
Calculated: -
Scaling: -
Unit selection: -
Max
600000000.00 [µs]
Calculated: -
Scaling: -
Unit selection: -
Max
600000000.00 [µs]
Calculated: -
Scaling: -
Unit selection: -
Max
100000000.00 [µs]
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Data type: FloatingPoint32
Data set: -
Factory setting
300.00 [rpm]
Data type: FloatingPoint32
Data set: -
Factory setting
100000.00 [µs]
Data type: FloatingPoint32
Data set: -
Factory setting
600000000.00 [µs]
Data type: FloatingPoint32
Data set: -
Factory setting
40000000.00 [µs]