Siemens CU240B-2 Parameter Manual page 348

Table of Contents

Advertisement

Parameters
List of Parameters
p9506
SI Motion function specification (processor 1) / SI Mtn fct_spc P1
CU240E-2 DP F
Access level: 3
CU240E-2 F
Can be changed: C(95)
Units group: -
Min
1
Description:
Sets the function specification for the safe motion monitoring.
Value:
1:
3:
Dependency:
Refer to: C01711
p9507
SI Motion function configuration (processor 1) / SI Mtn config P1
PM240
Access level: 3
PM250
Can be changed: C(95)
PM260
Units group: -
CU240E-2 DP F
CU240E-2 F
Min
-
Description:
Sets the function configuration for safe motion monitoring.
Bit field:
Bit
Signal name
00
Extended message acknowledgement
01
Setpoint velocity limit for STOP F
Dependency:
Refer to: C01711
Note:
Re bit 00:
When the function is activated, a safety-relevant acknowledgement (internal event acknowledge) can be performed
by selecting/deselecting STO.
Re bit 01:
When the function is activated, the active setpoint velocity limit (CO: r9733) is set to zero when STOP F is active.
1-348
Safety without encoder
Safety without encoder with accel_monitoring/delay time
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Calculated: -
Scaling: -
Unit selection: -
Max
3
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
No
Data type: Integer16
Data set: -
Factory setting
1
Data type: Unsigned32
Data set: -
Factory setting
0011 bin
0 signal
No
Yes
© Siemens AG 2011 All Rights Reserved
FP
-
-

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120Cu240e-2Cu240b-2 dpCu240e-2 dpCu240e-2 fCu240e-2 dp f

Table of Contents