Siemens CU240B-2 Parameter Manual page 152

Table of Contents

Advertisement

Parameters
List of Parameters
r1112
CO: Speed setpoint after minimum limiting / n_set n. min_lim
Access level: 4
Can be changed: -
Units group: 3_1
Min
- [rpm]
Description:
Displays the speed setpoint after the minimum limiting.
Dependency:
Refer to: p1091, p1092, p1093, p1094, p1101
p1113[0...n]
BI: Setpoint inversion / Setp inv
CU240B-2
Access level: 3
CU240E-2
Can be changed: T
CU240E-2 F
Units group: -
Min
-
Description:
Sets the signal source to invert the setpoint.
Dependency:
Refer to: r1198
Caution:
If the technology controller is being used as the speed main setpoint (p2251 = 0), do not invert the setpoint using
p1113 when the technology controller is enabled because this can cause the speed to change suddenly and lead to
positive couplings in the control loop.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1113[0...n]
BI: Setpoint inversion / Setp inv
CU240B-2 DP
Access level: 3
CU240E-2 DP
Can be changed: T
CU240E-2 DP F
Units group: -
Min
-
Description:
Sets the signal source to invert the setpoint.
Dependency:
Refer to: r1198
Caution:
If the technology controller is being used as the speed main setpoint (p2251 = 0), do not invert the setpoint using
p1113 when the technology controller is enabled because this can cause the speed to change suddenly and lead to
positive couplings in the control loop.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
r1114
CO: Setpoint after the direction limiting / Setp after limit
Access level: 3
Can be changed: -
Units group: 3_1
Min
- [rpm]
Description:
Displays the speed/velocity setpoint after the changeover and limiting the direction.
1-152
Calculated: -
Scaling: p2000
Unit selection: p0505
Max
- [rpm]
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: p2000
Unit selection: p0505
Max
- [rpm]
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Data type: FloatingPoint32
Data set: -
Factory setting
- [rpm]
Data type: U32 / Binary
Data set: CDS, p0170
Factory setting
[0] 722.1
[1] 0
[2] 0
[3] 0
Data type: U32 / Binary
Data set: CDS, p0170
Factory setting
[0] 2090.11
[1] 0
[2] 0
[3] 0
Data type: FloatingPoint32
Data set: -
Factory setting
- [rpm]
© Siemens AG 2011 All Rights Reserved

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120Cu240e-2Cu240b-2 dpCu240e-2 dpCu240e-2 fCu240e-2 dp f