Siemens CU240B-2 Parameter Manual page 42

Table of Contents

Advertisement

Parameters
List of Parameters
r0094
CO: Transformation angle / Transformat_angle
Access level: 3
Can be changed: -
Units group: -
Min
- [°]
Description:
Displays the transformation angle.
Dependency:
Refer to: r1778
Note:
The transformation angle corresponds to the electrical commutation angle.
p0100
IEC/NEMA mot stds / IEC/NEMA mot stds
Access level: 1
Can be changed: C(1)
Units group: -
Min
0
Description:
Defines whether the motor and drive converter power settings (e.g. rated motor power - p0307) are expressed in
[kW] or [hp].
Depending on the selection, the rated motor frequency (p0310) is either set to 50 Hz or 60 Hz.
For p0100 = 0, 2, the following applies: The power factor (p0308) should be parameterized.
For p0100 = 1, the following applies: The efficiency (p0309) should be parameterized.
Value:
0:
1:
2:
Dependency:
If p0100 is changed, all of the rated motor parameters are reset. Only then are possible unit changeovers made.
The units of all motor parameters are changed that are involved in the selection of IEC or NEMA (e.g. r0206, p0307,
r0333, r0334, p0341, p0344, r1969).
Refer to: r0206, p0210, p0300, p0304, p0305, p0307, p0308, p0309, p0310, p0311, p0314, p0320, p0322, p0323,
p0335, r0337, p1800
Note:
The parameter value is not reset when the factory setting is restored (p0010 = 30, p0970).
p0170
Number of Command Data Sets (CDS) / CDS count
Access level: 2
Can be changed: C(15)
Units group: -
Min
2
Description:
Sets the number of Command Data Sets (CDS).
Dependency:
Refer to: p0010, r3996
Notice:
When the data sets are created, short-term communication interruptions may occur.
Note:
It is possible to toggle between command parameters (BICO parameters) using this data set changeover.
p0180
Number of Drive Data Sets (DDS) / DDS count
Access level: 3
Can be changed: C(15)
Units group: -
Min
1
Description:
Sets the number of Drive Data Sets (DDS).
Dependency:
Refer to: p0010, r3996
Notice:
When the data sets are created, short-term communication interruptions may occur.
1-42
IEC-Motor (50 Hz, SI units)
NEMA motor (60 Hz, US units)
NEMA motor (60 Hz, SI units)
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Calculated: -
Scaling: p2005
Unit selection: -
Max
- [°]
Calculated: -
Scaling: -
Unit selection: -
Max
2
Calculated: -
Scaling: -
Unit selection: -
Max
4
Calculated: -
Scaling: -
Unit selection: -
Max
4
Data type: FloatingPoint32
Data set: -
Factory setting
- [°]
Data type: Integer16
Data set: -
Factory setting
0
Data type: Unsigned8
Data set: -
Factory setting
2
Data type: Unsigned8
Data set: -
Factory setting
1
© Siemens AG 2011 All Rights Reserved