Safety Integrated commissioning
p0010 = 95
SI password inp
p9761
SI password new
p9762
SI ackn password
p9763
<1>
Comparator, refer to [1021]
<2>
Analog signal memory, refer to [1021]
<3>
The target checksum must be equal to the actual checksum.
1
2
Safety Integrated
SI Motion, Parameter Manager
Changing safety parameters
Safety parameterizing enable
Enter password
&
=
x
y
<1>
SET
=
Effective password
y = x
<2>
<1>
Resetting safety parameters
Inhibit safety functions
p9301 = 0
p9501 = 0
&
p9601 = 0
[2810.3]
p9801 = 0
[2810.3]
3
4
SI Mtn act CRC P1
SI Mtn setp CRC P1
r9728
<3>
=
Safety parameter
p9300 ... p9399
p9500 ... p9599
p10002 ... p10152
can be changed
Checksum check
=
<3>
SI Mtn act CRC P2
SI Mtn setp CRC P2
r9398
p0010 unequal 95
commissioning mode
Safety parameter
p9300 … p9399
p9500 ... p9599
p10002 ... p10152
can be reset to
factory settings via
p0970, p3900
5
6
Function diagram
FP_2846_97_53.vsd
G120 CU240E-2 F/DP F
13.12.2010
V4.4
p9729
<1>
Safety parameters
p9300 … p9399
p9500 ... p9599
p10002 ... p10152
are valid after
&
save.
STARTER issues a
message if a
POWER ON is
for safety
required
parameters
<1>
p9399
Exit safety
7
8
- 2846 -

Hide quick links: