Parameters
List of Parameters
p1052[0...n]
CI: Speed limit RFG negative direction of rotation / n_limit RFG neg
CU240E-2 DP F
Access level: 3
CU240E-2 F
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source for the speed limit of the negative direction on the ramp-function generator input.
p1055[0...n]
BI: Jog bit 0 / Jog bit 0
CU240B-2
Access level: 3
CU240E-2
Can be changed: T
CU240E-2 F
Units group: -
Min
-
Description:
Sets the signal source for jog 1.
Dependency:
Refer to: p0840, p1058
Notice:
The drive is enabled for jogging using BI: p1055 or BI: p1056.
The command "ON/OFF1" can be issued using BI: p0840 or using BI: p1055/p1056.
Only the signal source that was used to power up can also be used to power down again.
p1055[0...n]
BI: Jog bit 0 / Jog bit 0
CU240B-2 DP
Access level: 3
CU240E-2 DP
Can be changed: T
CU240E-2 DP F
Units group: -
Min
-
Description:
Sets the signal source for jog 1.
Dependency:
Refer to: p0840, p1058
Notice:
The drive is enabled for jogging using BI: p1055 or BI: p1056.
The command "ON/OFF1" can be issued using BI: p0840 or using BI: p1055/p1056.
Only the signal source that was used to power up can also be used to power down again.
p1056[0...n]
BI: Jog bit 1 / Jog bit 1
CU240B-2
Access level: 3
CU240E-2
Can be changed: T
CU240E-2 F
Units group: -
Min
-
Description:
Sets the signal source for jog 2.
Dependency:
Refer to: p0840, p1059
Notice:
The drive is enabled for jogging using BI: p1055 or BI: p1056.
The command "ON/OFF1" can be issued using BI: p0840 or using BI: p1055/p1056.
Only the signal source that was used to power up can also be used to power down again.
1-144
Calculated: -
Scaling: p2000
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Data type: U32 / FloatingPoint32
Data set: CDS, p0170
Factory setting
9733[1]
Data type: U32 / Binary
Data set: CDS, p0170
Factory setting
0
Data type: U32 / Binary
Data set: CDS, p0170
Factory setting
[0] 0
[1] 722.0
[2] 0
[3] 0
Data type: U32 / Binary
Data set: CDS, p0170
Factory setting
0
© Siemens AG 2011 All Rights Reserved

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120Cu240e-2Cu240b-2 dpCu240e-2 dpCu240e-2 fCu240e-2 dp f

Table of Contents