Siemens CU240B-2 Parameter Manual page 367

Table of Contents

Advertisement

r9728[0...2]
SI Motion actual checksum SI parameters (processor 1) / SI Mtn act CRC P1
CU240E-2 DP F
Access level: 3
CU240E-2 F
Can be changed: -
Units group: -
Min
-
Description:
Displays the checksum over the checked Safety Integrated parameters of the motion monitoring functions (actual
checksum).
Index:
[0] = Checksum over SI parameters for motion monitoring
[1] = Checksum over SI parameters for actual values
[2] = Checksum over SI parameters for hardware
Dependency:
Refer to: p9729
Refer to: F01680
p9729[0...2]
SI Motion setpoint checksum SI parameters (processor 1) / SI Mtn setp CRC P1
CU240E-2 DP F
Access level: 3
CU240E-2 F
Can be changed: C(95)
Units group: -
Min
0000 hex
Description:
Sets the checksum using the checksum-tested Safety Integrated parameters for motion monitoring functions (refer-
ence checksum).
Index:
[0] = Checksum over SI parameters for motion monitoring
[1] = Checksum over SI parameters for actual values
[2] = Checksum over SI parameters for hardware
Dependency:
Refer to: r9728
Refer to: F01680
r9732
SI Motion velocity resolution / SI Mtn v_res
Access level: 3
CU240E-2 DP F
Can be changed: -
CU240E-2 F
Units group: -
Min
- [rpm]
Description:
Displays the safe velocity resolution (load side).
Setpoints for velocity limits or parameter changes for velocities below this threshold have no effect.
Note:
This parameter does not provide any information about the actual accuracy of the velocity sensing. This depends
on the type of actual value sensing, the gear factors as well as the quality of the encoder being used.
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
FFFF FFFF hex
Calculated: -
Scaling: -
Unit selection: -
Max
- [rpm]
Parameters
List of Parameters
Data type: Unsigned32
Data set: -
Factory setting
-
Data type: Unsigned32
Data set: -
Factory setting
0000 hex
Data type: FloatingPoint32
Data set: -
Factory setting
- [rpm]
1-367

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120Cu240e-2Cu240b-2 dpCu240e-2 dpCu240e-2 fCu240e-2 dp f

Table of Contents