Siemens CU240B-2 Parameter Manual page 97

Table of Contents

Advertisement

r0755[0...1]
CO: CU analog inputs actual value in percent / CU AI value in %
Access level: 2
Can be changed: -
Units group: -
Min
- [%]
Description:
Displays the currently referred input value of the analog inputs.
When interconnected, the signals are referred to the reference quantities p200x and p205x.
Index:
[0] = AI0 (T. 3/4)
[1] = AI1 (T. 10/11)
Note:
AI: Analog Input
T: Terminal
p0756[0...1]
CU analog inputs type / CU AI type
Access level: 2
Can be changed: U, T
Units group: -
Min
0
Description:
Sets the type of analog inputs.
p0756[0...1] = 0, 1, 4 corresponds to a voltage input (r0752, p0757, p0759 are displayed in V).
p0756[0...1] = 2, 3 corresponds to a current input (r0752, p0757, p0759 are displayed in mA).
In addition, the associated DIP switch must be set.
For the voltage input, DIP switch AI0/1 must be set to "U".
For the current input, DIP switch AI0/1 or AI2 must be set to "I".
Value:
0:
1:
2:
3:
4:
8:
Index:
[0] = AI0 (T. 3/4)
[1] = AI1 (T. 10/11)
Warning:
The maximum voltage difference between analog input terminals AI+, AI-, and the ground must not exceed 35 V.
If the system is operated when the load resistor is switched on (DIP switch set to "I"), the voltage between differen-
tial inputs AI+ and AI- must not exceed 10 V or the injected 80 mA current otherwise the input will be damaged.
Note:
When changing p0756 , the parameters of the scaling characteristic (p0757, p0758, p0759, p0760) are overwritten
with the following default values:
For p0756 = 0, 1, 4, p0757 is set to 0.0 V, p0758 = 0.0 %, p0759 = 10.0 V and p0760 = 100.0 %.
For p0756 = 2, p0757 is set to 0.0 mA, p0758 = 0.0 %, p0759 = 20.0 mA and p0760 = 100.0 %.
For p0756 = 3, p0757 is set to 4.0 mA, p0758 = 0.0 %, p0759 = 20.0 mA and p0760 = 100.0 %.
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Unipolar voltage input (0 V ... +10 V)
Unipolar voltage input monitored (+2 V ... +10 V)
Unipolar current input (0 mA ... +20 mA)
Unipolar current input monitored (+4 mA to +20 mA)
Bipolar voltage input (-10 V ... +10 V)
No sensor connected
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
- [%]
Calculated: -
Scaling: -
Unit selection: -
Max
8
Parameters
List of Parameters
Data type: FloatingPoint32
Data set: -
Factory setting
- [%]
Data type: Integer16
Data set: -
Factory setting
[0] 4
[1] 4
1-97