Siemens CU240B-2 Parameter Manual page 180

Table of Contents

Advertisement

Parameters
List of Parameters
p1250[0...n]
Vdc controller proportional gain / Vdc_ctrl Kp
PM230
Access level: 3
PM240
Can be changed: U, T
Units group: -
Min
0.00
Description:
Sets the proportional gain for the DC-link voltage controller (Vdc_min controller, Vdc_max controller).
Dependency:
The effective proportional gain is obtained taking into account p1243 (Vdc_max controller dynamic factor) and the
DC link capacitance of the power unit.
p1251[0...n]
Vdc controller integral time / Vdc_ctrl Tn
PM230
Access level: 3
PM240
Can be changed: U, T
Units group: -
Min
0 [ms]
Description:
Sets the integral time for the DC-link voltage controller (Vdc_min controller, Vdc_max controller).
Dependency:
The effective integral time is obtained taking into account p1243 (Vdc_max controller dynamic factor).
Note:
p1251 = 0: The integral component is de-activated.
p1252[0...n]
Vdc controller rate time / Vdc_ctrl t_rate
PM230
Access level: 3
PM240
Can be changed: U, T
Units group: -
Min
0 [ms]
Description:
Sets the rate time constant for the DC-link voltage controller (Vdc_min controller, Vdc_max controller).
Dependency:
The effective rate time is obtained taking into account p1243 (Vdc_max controller dynamic factor).
p1254
Vdc_max controller automatic ON level detection / Vdc_max SenseOnLev
PM230
Access level: 3
Can be changed: U, T
Units group: -
Min
0
Description:
Activates/de-activates the automatic sensing of the switch-in level for the Vdc_max controller.
Value:
0:
1:
p1254
Vdc_max controller automatic ON level detection / Vdc_max SenseOnLev
PM240
Access level: 3
Can be changed: U, T
Units group: -
Min
0
Description:
Activates/de-activates the automatic sensing of the switch-in level for the Vdc_max controller.
Value:
0:
1:
1-180
Automatic detection inhibited
Automatic detection enabled
Automatic detection inhibited
Automatic detection enabled
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Calculated: -
Scaling: -
Unit selection: -
Max
100.00
Calculated: -
Scaling: -
Unit selection: -
Max
10000 [ms]
Calculated: -
Scaling: -
Unit selection: -
Max
1000 [ms]
Calculated: -
Scaling: -
Unit selection: -
Max
1
Calculated: -
Scaling: -
Unit selection: -
Max
1
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
1.00
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
0 [ms]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
0 [ms]
Data type: Integer16
Data set: -
Factory setting
0
Data type: Integer16
Data set: -
Factory setting
1
© Siemens AG 2011 All Rights Reserved

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120Cu240e-2Cu240b-2 dpCu240e-2 dpCu240e-2 fCu240e-2 dp f

Table of Contents