Siemens CU240B-2 Parameter Manual page 291

Table of Contents

Advertisement

p2177[0...n]
Motor locked delay time / Mot lock t_del
Access level: 3
Can be changed: U, T
Units group: -
Min
0.000 [s]
Description:
Sets the delay time for the message "Motor locked" (BO: r2198.6).
Dependency:
Refer to: p0500, p2175, r2198
Note:
The following applies for sensorless vector control:
At low speeds a locked motor can only be detected if no change is made to open-loop speed controlled operation. If
this is the case, the value in p2177 must be reduced accordingly before time p2177 has elapsed in order to detect
the locked state reliably.
p2178[0...n]
Motor stalled delay time / Mot stall t_del
Access level: 3
Can be changed: U, T
Units group: -
Min
0.000 [s]
Description:
Sets the delay time for the message "Motor stalled" (BO: r2198.7).
Dependency:
Refer to: r2198
Note:
In the open-loop speed controlled operating range (see p1755, p1756), vector control stall monitoring depends on
threshold p1745.
At higher speeds, the difference between flux setpoint r0083 and flux actual value r0084 is monitored.
p2179[0...n]
Output load identification current limit / Outp_ld iden I_lim
Access level: 3
Can be changed: U, T
Units group: 6_2
Min
0.00 [Arms]
Description:
Sets the current limit for output load identification.
Dependency:
Refer to: p2180
Notice:
For synchronous motors the output current can be almost zero under no load conditions.
Note:
A missing output load condition exists if the motor is either not connected or a phase has failed.
p2180[0...n]
Missing output load delay time / No load t_delay
Access level: 3
Can be changed: U, T
Units group: -
Min
0 [ms]
Description:
Sets the delay time to detect a missing output load.
Dependency:
Refer to: p2179
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Calculated: p0340 = 1,3,5
Scaling: -
Unit selection: -
Max
65.000 [s]
Calculated: p0340 = 1,3
Scaling: -
Unit selection: -
Max
10.000 [s]
Calculated: p0340 = 1,3,5
Scaling: p2002
Unit selection: p0505
Max
1000.00 [Arms]
Calculated: -
Scaling: -
Unit selection: -
Max
10000 [ms]
Parameters
List of Parameters
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
3.000 [s]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
0.010 [s]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
0.00 [Arms]
Data type: Unsigned16
Data set: DDS, p0180
Factory setting
2000 [ms]
1-291

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120Cu240e-2Cu240b-2 dpCu240e-2 dpCu240e-2 fCu240e-2 dp f

Table of Contents