Siemens CU240B-2 Parameter Manual page 360

Table of Contents

Advertisement

Parameters
List of Parameters
p9601
SI enable, functions integrated in the drive (processor 1) / SI enable fct P1
PM240
Access level: 3
PM250
Can be changed: C(95)
PM260
Units group: -
CU240E-2 F
Min
-
Description:
Sets the enable signals for safety functions on processor 1 that are integrated in the drive.
Not all of the settings listed below will be permissible, depending on the Control Unit being used:
- p9601 = 0: Safety functions integrated in the drive disabled.
- p9601 = 1: STO enabled via terminals. Permissible if r9771.0 = 1.
- p9601 = 4: Motion monitoring functions integrated in the drive enabled via an integrated F-DI. Permissible if
r9771.5 = 1.
- p9601 = 8: STO enabled via PROFIsafe. Permissible if r9771.6 = 1.
- p9601 = 9: STO enabled via PROFIsafe and STO via terminals. Permissible if r9771.6 = 1.
- p9601 = 12: Motion monitoring functions integrated in the drive enabled via PROFIsafe. Permissible if r9771.4 = 1.
- p9601 = 13: Motion monitoring functions integrated in the drive enabled via PROFIsafe and STO via terminals.
Permissible if r9771.4 = 1.
Bit field:
Bit
Signal name
00
Enable STO via terminals (processor 1)
02
Motion monitoring functions integr. in the
drive (processor 1)
Dependency:
Refer to: r9771, p9801
Note:
A change only becomes effective after a POWER ON.
F-DI: Failsafe Digital Input.
STO: Safe Torque Off
p9610
SI PROFIsafe address (processor 1) / SI PROFIsafe P1
CU240E-2 DP
Access level: 3
CU240E-2 DP F
Can be changed: C(95)
Units group: -
Min
0000 hex
Description:
Sets the PROFIsafe address for processor 1.
Dependency:
Refer to: p9810
p9650
SI F-DI changeover tolerance time (processor 1) / SI F-DI_chg tol P1
CU240E-2
Access level: 3
CU240E-2 DP
Can be changed: C(95)
CU240E-2 DP F
Units group: -
CU240E-2 F
Min
0.00 [ms]
Description:
Sets the tolerance time for the changeover of the failsafe digital input for STO on processor 1.
An F-DI changeover is not effective simultaneously due to the different runtimes in the two monitoring channels.
After an F-DI changeover, dynamic data is not subject to a crosswise data comparison during this tolerance time.
Dependency:
Refer to: p9850
Note:
For a crosswise data comparison between p9650 and p9850, a difference of one Safety monitoring clock cycle is
tolerated.
The parameterized time is internally rounded-off to an integer multiple of the monitoring clock cycle.
F-DI: Failsafe Digital Input
1-360
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Enable
Enable
Calculated: -
Scaling: -
Unit selection: -
Max
FFFE hex
Calculated: -
Scaling: -
Unit selection: -
Max
2000.00 [ms]
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Data type: Unsigned32
Data set: -
Factory setting
0000 bin
0 signal
Inhibit
Inhibit
Data type: Unsigned16
Data set: -
Factory setting
0000 hex
Data type: FloatingPoint32
Data set: -
Factory setting
500.00 [ms]
© Siemens AG 2011 All Rights Reserved
FP
2810
-