p2286[0...n]
BI: Hold technology controller integrator / Tec_ctr integ stop
Access level: 3
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source to hold the integrator for the technology controller.
p2289[0...n]
CI: Technology controller pre-control signal / Tec_ctrl prectrl
Access level: 3
Can be changed: U, T
Units group: -
Min
-
Description:
Sets the signal source for the pre-control signal of the technology controller.
p2291
CO: Technology controller maximum limiting / Tec_ctrl max_limit
Access level: 3
Can be changed: U, T
Units group: -
Min
-200.00 [%]
Description:
Sets the maximum limit of the technology controller.
Dependency:
Refer to: p2292
Caution:
The maximum limit must always be greater than the minimum limit (p2291 > p2292).
p2292
CO: Technology controller minimum limiting / Tec_ctrl min_lim
Access level: 3
Can be changed: U, T
Units group: -
Min
-200.00 [%]
Description:
Sets the minimum limit of the technology controller.
Dependency:
Refer to: p2291
Caution:
The maximum limit must always be greater than the minimum limit (p2291 > p2292).
p2293
Technology controller ramp-up/ramp-down time / Tec_ctr ramp up/dn
Access level: 3
Can be changed: U, T
Units group: -
Min
0.00 [s]
Description:
Sets the ramping time for the output signal of the technology controller.
Dependency:
Refer to: p2291, p2292
Note:
The time refers to the set maximum and minimum limits (p2291, p2292).
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
200.00 [%]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
200.00 [%]
Calculated: -
Scaling: -
Unit selection: -
Max
100.00 [s]
Parameters
List of Parameters
Data type: U32 / Binary
Data set: CDS, p0170
Factory setting
56.13
Data type: U32 / FloatingPoint32
Data set: CDS, p0170
Factory setting
0
Data type: FloatingPoint32
Data set: -
Factory setting
100.00 [%]
Data type: FloatingPoint32
Data set: -
Factory setting
0.00 [%]
Data type: FloatingPoint32
Data set: -
Factory setting
1.00 [s]
1-311

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120Cu240e-2Cu240b-2 dpCu240e-2 dpCu240e-2 fCu240e-2 dp f

Table of Contents