Siemens CU240B-2 Parameter Manual page 276

Table of Contents

Advertisement

Parameters
List of Parameters
r2110[0...63]
Alarm number / Alarm number
Access level: 2
Can be changed: -
Units group: -
Min
-
Description:
This parameter is identical to r2122.
p2111
Alarm counter / Alarm counter
Access level: 3
Can be changed: U, T
Units group: -
Min
0
Description:
Number of alarms that have occurred after the last reset.
Dependency:
When p2111 is set to 0, the following is initiated:
- all of the alarms of the alarm buffer that have gone [0...7] are transferred into the alarm history [8...63].
- the alarm buffer [0...7] is deleted.
Refer to: r2110, r2122, r2123, r2124, r2125
Note:
The parameter is reset to 0 at POWER ON.
p2112[0...n]
BI: External alarm 1 / External alarm 1
Access level: 3
Can be changed: U, T
Units group: -
Min
-
Description:
Sets the signal source for external alarm 1.
Dependency:
Refer to: A07850
Note:
An external alarm is triggered with a 1/0 signal.
r2114[0...1]
System runtime total / Sys runtime tot
Access level: 3
Can be changed: -
Units group: -
Min
-
Description:
Displays the total system runtime for the drive unit.
The time comprises r2114[0] (milliseconds) and r2114[1] (days).
After r2114[0] has reached a value of 86.400.000 ms (24 hours) this value is reset and r2114[1] is incremented.
Index:
[0] = Milliseconds
[1] = Days
Dependency:
Refer to: r0948, r2109, r2123, r2125, r2130, r2136, r2145, r2146
Note:
When the electronic power supply is switched out, the counter values are saved.
After the drive unit is powered up, the counter continues to run with the last value that was saved.
1-276
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
65535
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Data type: Unsigned16
Data set: -
Factory setting
-
Data type: Unsigned16
Data set: -
Factory setting
0
Data type: U32 / Binary
Data set: CDS, p0170
Factory setting
1
Data type: Unsigned32
Data set: -
Factory setting
-
© Siemens AG 2011 All Rights Reserved

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120Cu240e-2Cu240b-2 dpCu240e-2 dpCu240e-2 fCu240e-2 dp f

Table of Contents